| 2023-02-28 15:16:24 | E23020005 ??? 100 EL BRAVO ??? INITIAL SUBMITTAL REVIEW |
| | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | 1. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 2. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER (AVERAGE, MAXIMUM AND PEAK) |
| | AND FIRE FLOW DEMANDS. |
| | 3. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING |
| | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY |
| | SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND |
| | IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS, |
| | AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH |
| | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES |
| | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, |
| | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND |
| | MANHOLES AND PROFILES OF SANITARY SEWER LINES. PLAN |
| | VIEW SHALL SHOW ALL EXISTING AND PROPOSED UNDERGROUND |
| | UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS, |
| | AND CABLEVISION & TELECOMMUNICATION FACILITIES LOCATED |
| | ON THE RIGHT-OF-WAY. |
| | 4. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS. |
| | 5. PLEASE LABEL 2??? COPPER CONNECTING TO PROPOSED |
| | 2???DOUBLE DETECTOR AS EXISTING OR PROPOSED. |
| | 6. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING |
| | AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR |
| | GREATER. PLEASE SHOW LENGTH OF 2 IN. FIRE LINE FROM |
| | BACKFLOW TO BUILDING. |
| | 7. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER |
| | CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES. |
| | 8. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE |
| | PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW |
| | DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING |
| | USC APPROVED LEAD-FREE DESIGN. |
| | 9. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | 10. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (E-XXXXXXXX). |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | -THERE ARE SEVERAL REFERENCES TO BACKFLOW ASSEMBLY |
| | 975XLS. I THINK THAT MAY BE A TYPO. THE LEAD FREE |
| | VERSION RP IS TYPICALLY WILKINS ZURN 975XL2. PLEASE |
| | UPDATE. |
| | -ON THE LABELS FOR THE DOMESTIC BACKFLOW ASSEMBLIES, |
| | THERE IS WORDING ABOUT DIRECTION TEST COCKS SHOULD BE |
| | FACING WHEN ORDERED. DIRECTION SHOULD BE EAST INSTEAD |
| | OF NORTH. |
| | -CANNOT TEE/TAP FIRELINE OFF THE COPPER WATER SERVICE |
| | PIPE FOR THE DOMESTIC 2 INCH METER. FIRELINE MAY ALSO |
| | NOT BE DOWNSTREAM OF THE DOMESTIC METER. |
| | -ON LABEL FOR THE DOMESTIC BACKFLOW ASSEMBLIES ADD |
| | REFERENCE TO STANDARD DETAIL WS6. |
| | -ON LABEL FOR THE FIRELINE BACKFLOW ASSEMBLY ADD |
| | REFERENCE TO STANDARD DETAIL WS5. |
| | -ON LABEL FOR THE WATER METER ADD REFERENCE TO STANDARD |
| | DETAIL WS1. |
| | -ON CALLOUT OF FIRELINE WATER SERVICE PIPE, SPECIFY K |
| | COPPER. |
| | -SHOW AND LABEL EXISTING AND PROPOSED SANITARY SEWER |
| | LATERALS, CLEANOUTS, AND MAINS. |
| | -THERE IS AT LEAST ONE EXISTING 1.5??? BACKFLOW |
| | ASSEMBLY NEAR THE EXISTING WATER METER. WILL IT REMAIN |
| | OR BE REMOVED? |
| | -THERE ARE CURRENTLY A LOT OF BUSHES WHERE THE BACKFLOW |
| | ASSEMBLIES ARE PROPOSED. ADD NOTE THAT BUSHES SHOULD |
| | NOT ENCROACH WITHIN 18 INCHES OF BACKFLOW ASSEMBLIES. |
| | -SHOW AND LABEL ALL FRANCHISE UTILITIES NEAR WORK AREA. |
| | -ADD FIRE FLOW CALCULATIONS AS DIRECTED IN STANDARD |
| | DETAIL WS5 NOTE 9. |
| | -ADD WATER SERVICE STANDARD DETAIL WS2 TO SHEET WS3 |
| | -CANNOT LOCATE WATER DEMAND CALCULATIONS. NEED ADD TO |
| | PLAN SET. |
| | -FIRELINE WATER SERVICE NEEDS A VALVE TO TURN IT ON AND |
| | OFF. |
| | -VERIFY THAT PRIVATE FIRE SYSTEM WILL NOT HAVE ADDED |
| | CHEMICALS, WILL NOT FEED A COOLING TOWER, AND WILL NOT |
| | HAVE AN AUXILIARY WATER SUPPLY SUCH AS A WELL. |
| | -HOW MANY FEET IS EACH OF THE NEW PLUMBING PIPE |
| | CONTINUATIONS TO THE BUILDING? |
| | |
| | |
| | COMMENTS FROM RICKY ELIZONDO, E.I., UTILITIES PLANS |
| | EXAMINER, PUBLIC UTILITIES [email protected] |
| | 561-764-8010 (CELL) |
| | -SHOW ENTIRE CONFIGURATION OF FIRE HYDRANT CONNECTION. |
| | -EXTRA WATER METER APPEARS TO BE SHOWN ON DRAWINGS |
| | -FIRE LINE CONNECTION MUST BE SEPARATE FROM THE |
| | DOMESTIC LINE. A SEPARATE TAP WILL BE REQUIRED |
| | -SHOW ALL UTILITIES, INCLUDING DRY UTILITIES, SEWER, |
| | AND STORMWATER. |
| | -CURRENT LOCATION OF PROPOSED BACKFLOWS APPEAR TO BE IN |
| | BUSH AREAS. PLEASE EVALUATE |
| | -APPARENT GALVANIZED PIPE DIRECTLY SOUTH OF PROPERTY |
| | MAY REQUIRE REMOVAL |
| | |
| | |
| | |