Plan Review Details - Project E23020005
Plan Review Stops For Project E23020005
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 02-28-2023 Cont ID  
Sent By lquinone Date 02-28-2023 Time 15:15 Rev Time 0.00
Received By lquinone Date 02-28-2023 Time 15:15 Sent To  
Notes
2023-02-28 15:16:24E23020005 ??? 100 EL BRAVO ??? INITIAL SUBMITTAL REVIEW
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 1. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 2. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS.
 3. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. PLAN
 VIEW SHALL SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES LOCATED
 ON THE RIGHT-OF-WAY.
 4. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS.
 5. PLEASE LABEL 2??? COPPER CONNECTING TO PROPOSED
 2???DOUBLE DETECTOR AS EXISTING OR PROPOSED.
 6. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER. PLEASE SHOW LENGTH OF 2 IN. FIRE LINE FROM
 BACKFLOW TO BUILDING.
 7. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 8. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 9. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 10. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -THERE ARE SEVERAL REFERENCES TO BACKFLOW ASSEMBLY
 975XLS. I THINK THAT MAY BE A TYPO. THE LEAD FREE
 VERSION RP IS TYPICALLY WILKINS ZURN 975XL2. PLEASE
 UPDATE.
 -ON THE LABELS FOR THE DOMESTIC BACKFLOW ASSEMBLIES,
 THERE IS WORDING ABOUT DIRECTION TEST COCKS SHOULD BE
 FACING WHEN ORDERED. DIRECTION SHOULD BE EAST INSTEAD
 OF NORTH.
 -CANNOT TEE/TAP FIRELINE OFF THE COPPER WATER SERVICE
 PIPE FOR THE DOMESTIC 2 INCH METER. FIRELINE MAY ALSO
 NOT BE DOWNSTREAM OF THE DOMESTIC METER.
 -ON LABEL FOR THE DOMESTIC BACKFLOW ASSEMBLIES ADD
 REFERENCE TO STANDARD DETAIL WS6.
 -ON LABEL FOR THE FIRELINE BACKFLOW ASSEMBLY ADD
 REFERENCE TO STANDARD DETAIL WS5.
 -ON LABEL FOR THE WATER METER ADD REFERENCE TO STANDARD
 DETAIL WS1.
 -ON CALLOUT OF FIRELINE WATER SERVICE PIPE, SPECIFY K
 COPPER.
 -SHOW AND LABEL EXISTING AND PROPOSED SANITARY SEWER
 LATERALS, CLEANOUTS, AND MAINS.
 -THERE IS AT LEAST ONE EXISTING 1.5??? BACKFLOW
 ASSEMBLY NEAR THE EXISTING WATER METER. WILL IT REMAIN
 OR BE REMOVED?
 -THERE ARE CURRENTLY A LOT OF BUSHES WHERE THE BACKFLOW
 ASSEMBLIES ARE PROPOSED. ADD NOTE THAT BUSHES SHOULD
 NOT ENCROACH WITHIN 18 INCHES OF BACKFLOW ASSEMBLIES.
 -SHOW AND LABEL ALL FRANCHISE UTILITIES NEAR WORK AREA.
 -ADD FIRE FLOW CALCULATIONS AS DIRECTED IN STANDARD
 DETAIL WS5 NOTE 9.
 -ADD WATER SERVICE STANDARD DETAIL WS2 TO SHEET WS3
 -CANNOT LOCATE WATER DEMAND CALCULATIONS. NEED ADD TO
 PLAN SET.
 -FIRELINE WATER SERVICE NEEDS A VALVE TO TURN IT ON AND
 OFF.
 -VERIFY THAT PRIVATE FIRE SYSTEM WILL NOT HAVE ADDED
 CHEMICALS, WILL NOT FEED A COOLING TOWER, AND WILL NOT
 HAVE AN AUXILIARY WATER SUPPLY SUCH AS A WELL.
 -HOW MANY FEET IS EACH OF THE NEW PLUMBING PIPE
 CONTINUATIONS TO THE BUILDING?
  
  
 COMMENTS FROM RICKY ELIZONDO, E.I., UTILITIES PLANS
 EXAMINER, PUBLIC UTILITIES [email protected]
 561-764-8010 (CELL)
 -SHOW ENTIRE CONFIGURATION OF FIRE HYDRANT CONNECTION.
 -EXTRA WATER METER APPEARS TO BE SHOWN ON DRAWINGS
 -FIRE LINE CONNECTION MUST BE SEPARATE FROM THE
 DOMESTIC LINE. A SEPARATE TAP WILL BE REQUIRED
 -SHOW ALL UTILITIES, INCLUDING DRY UTILITIES, SEWER,
 AND STORMWATER.
 -CURRENT LOCATION OF PROPOSED BACKFLOWS APPEAR TO BE IN
 BUSH AREAS. PLEASE EVALUATE
 -APPARENT GALVANIZED PIPE DIRECTLY SOUTH OF PROPERTY
 MAY REQUIRE REMOVAL
  
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***