Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 2 Status F Date 06-22-2023 Cont ID  
Sent By lquinone Date 06-22-2023 Time 10:26 Rev Time 0.00
Received By lquinone Date 06-22-2023 Time 10:26 Sent To  
Notes
2023-06-22 10:27:24E23010043 - 512 CLEMATIS ST RESUB 4.21.23
  
 NO COMMENTS FROM LINDA QUINONES, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
 -ADD WATER SERVICE STANDARD DETAILS WS1 AND WS6 TO PLAN
 SET. RECOMMEND ADDING THEM TO IRRIGATION PLAN SET ALSO.
  
 -LANDSCAPING PLAN PLANT LOCATIONS CONFLICT WITH
 UTILITIES AND DOES NOT SHOW PROPOSED UTILITY LOCATIONS
 THAT MATCH CIVIL ENGINEERING PLAN. PLEASE INCLUDE
 UPDATED/REVISED LANDSCAPING PLAN IN RESUBMITTAL
 PACKAGE.
  
 -PROVIDE FOLLOW-UP AS REFERENCED IN LAST RESPONSE
 LETTER: [COMMUNICATE WITH GREG MIHALKO [email protected]
 FROM WPB PARKS DEPARTMENT CONCERNING THE PPRC
 IRRIGATION CONDITIONS AS THE EXISTING METER AND
 BACKFLOW PROPOSED TO BE RELOCATED IS FOR PARKS
 IRRIGATION. VERIFY HIS APPROVAL AND INDICATE WHAT HIS
 DIRECTIONS ARE. ALSO INDICATE IF ANOTHER METERED WATER
 SERVICE IS NEEDED, OR IF PRIVATE IRRIGATION WILL RUN
 OFF 3 INCH DOMESTIC METER.] - I EMAILED GREG MIHALKO ON
 APRIL 3 AND 4, 2023 AND WILL CONFIRM HIS APPROVAL OR
 DIRECTION ONCE I RECEIVE IT.
  
 -PLANS NEED TO BE SIGNED, SEALED, AND DATED BY LICENSED
 ENGINEER.
  
 -CALLOUT PIPE MATERIAL TYPE AND SIZE OF FIRE LINE WATER
 SERVICE AND WATER SERVICE FOR 3 INCH METER.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
  
 1. PROVIDE VERTICAL DATUM REFERENCE AND CONVERSION
 EQUATION TO NGVD1929 ON SHEETS 4 AND 5.
 2. PROVIDE FINAL DESIGN PLAN(S) FOR THE RTANKS. NOTE
 ONLY ONE SHEET, DATED 1/3/2023, WAS INCLUDED IN THE
 APRIL 2023 SUBMTITAL.
 3. REGARDING THE TYPICAL CROSS SECTIONS, PARTICULARLY
 AT DOORWAYS, REVIEW THE FLORIDA BUILDING CODE FOR THE
 MINIMUM REQUIRED LENGTH AND MAXIMUM ALLOWABLE SLOPE FOR
 LANDINGS OUTSIDE OF DOORS. THIS INFORMATION MAY BE
 FOUND IN CHAPTER 1010.1.5 AND 1010.1.6. REVISE THE
 AFFECTED SECTIONS AND VERIFY THE SIDEWALKS AT DOORWAYS
 WILL MEET THE EXISTING BACK OF SIDEWALK ELEVATION.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 PRIOR COMMENTS NOT ADDRESSED FROM APRIL 20, 2023
 -COMMENT 1: CITY???S RECORD SHOWS THERE ARE (2) WATER
 SERVICES SERVING 512 CLEMATIS STREET FROM CLEMATIS
 STREET. THESE SERVICES NEED TO BE CUT AND CAP AT THE
 MAIN ON CLEMATIS STREET. EXISTING WATER AND SEWER
 SERVICES CURRENTLY SERVING THE PROPERTY, IF NOT USED,
 NEEDS TO BE CUT AND CAP AT THE MAIN.
 -COMMENT 3: PROVIDE A PROFILE FOR THE PROPOSED SANITARY
 SEWER LATERAL FROM THE PROPOSED MANHOLE/POINT OF
 CONNECTION TO THE PROPOSED CLEAN-OUT/POINT OF SERVICE.
 CALL OUT ALL UTILITY CROSSINGS WITH HORIZONTAL AND
 VERTICAL CLEARANCES.
 -COMMENT 5: REFER TO APPLICABLE CITY STANDARD DETAILS
 FOR PROPOSED SEWER LATERAL CONNECTION AND PLACEMENT OF
 CLEANOUT (GS 1-8)
 -COMMENT 6: THE CONNECTION FROM THE GREASE TRAP NEED TO
 BE MADE NORTH OF THE PROPOSED CLEANOUT/POINT OF
 SERVICE. EOR TO CONFIRM WHETHER A SEPARATE CONNECTION
 IS REQUIRED FOR FLOWS FROM GREASE TRAP.
  
 PRIOR COMMENTS NOT ADDRESSED FROM FEBRUARY 2022 PPRC
 SUBMITTAL
 -COMMENT 2: REPLACE EXISTING SANITARY SEWER LINE
 FRONTING THE PROPERTY UP TO SANITARY MANHOLE ON
 QUADRILLE PLAZA DRIVE. THE LIMITS OF THE CITY???S
 CLEMATIS STREET SOUTH ALLEYWAY IMPROVEMENTS WILL START
 FROM THE SW CORNER OF 512 CLEMATIS PROPERTY HEADING
 WEST TO ROSEMARY.
 -COMMENT 3: PERFORM SOFTDIGS AS REQUIRED TO CALL OUT
 HORIZONTAL AND VERTICAL CLEARANCES, AS WELL AS TO
 CONFIRM EXISTENCE OF DRY UTILITIES AND
  
 NEW COMMENTS:
 1. PLAN SHEETS NEED TO BE SET UP TO PRINT TO SCALE ON
 11???X17???
 2. THIS PROJECT FALLS WITHIN LS 40 SERVICE BOUNDARY.
 MODIFY ON PLANS FROM LS 43 TO LS 40.
 3. CITY???S RECORD SHOWS THAT THE EXISTING WATER LINE
 IN THE ALLEYWAY IS NOT LOOPED AND IS POSSIBLY
 UNDERSIZED WEST OF QUADRILLE PLAZA DRIVE. THE EXISTING
 WATER MAIN FRONTING THE PROPERTY NEEDS TO BE REPLACED.
  
  
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 03-02-2023 Cont ID  
Sent By lquinone Date 03-02-2023 Time 15:45 Rev Time 0.00
Received By lquinone Date 03-02-2023 Time 15:44 Sent To  
Notes
2023-03-02 15:45:33E23010043 - 512 CLEMATIS ST 1.31.23 SUBMITTAL
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 4. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 6. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. PLEASE
 SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 7. PLEASE CUT AND CAP UTILITIES NOT IN USE AND REMOVE
 ANY ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM
 CITY RIGHT OF WAY.
 8. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 9. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS
 SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS
 SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY
 LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED
 ABOVE-GROUND ONLY.
 10. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA. SPECIFY LEAD FREE
 DESIGN ON ALL BACKFLOWS.
 11. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER.
 12. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 13. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY.
 14. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 15. PLEASE PROVIDE SANITARY ELEVATIONS AT MANHOLE
 TIE-IN.
 16. IF TRENCHING IN IN CITY-MAINTAINED ROADWAY AREAS
 ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION
 TRANSITION ON EACH SIDE OF PROPOSED TRENCH PER CITY OF
 WPB STANDARD DETAIL GC-4.
 17. PLEASE COORDINATE WITH PUBLIC UTILITIES ABOUT
 ACCEPTANCE OF PROPOSED 4 FT. SANITARY MANHOLE. (5 FT.
 IS PREFERRED.)
 18. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 19. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -ADD WORDING ???ABOVE-GROUND??? TO LABEL OF PROPOSED 3
 INCH METER AS WELL AS REFERENCE TO WATER SERVICE
 STANDARD DETAIL WS3.
 -THERE SHOULD BE A 4 INCH GATE VALVE AND BYPASS BEFORE
 REDUCER FOR PROPOSED 3 INCH METER PER WS3.
 -SEPARATE THE CALLOUT FOR THE 3 INCH RPPA WITH ANOTHER
 LEADER LINE AND ADD REFERENCE TO WATER SERVICE STANDARD
 DETAIL WS7.
 -VERIFY DCDA LOCATION IS ACCEPTABLE WITH FIRE MARSHAL
 LEDUC.
 -PROVIDE SIGNED AND SEALED FIRE FLOW CALCULATIONS AS
 DIRECTED IN NOTE 9 WS5.
 -ON LABEL FOR DCDA ADD REFERENCE TO WATER SERVICE
 STANDARD DETAIL WS5.
 -ADD SHEETS TO PLAN SET WITH ASSOCIATED WPB STANDARD
 DETAILS. SHOULD SEE AT LEAST WS5, WS3, WS7, WS1, WS2,
 WS6 AND POSSIBLY OTHERS.
 -PROVIDE SIGNED AND SEALED FLOW CALCULATIONS AS
 DIRECTED IN NOTE 7 WS7.
 -METER AND BACKFLOW LOCATIONS SEEM TO HAVE CHANGED
 SINCE PPRC. ENSURE LANDSCAPING TREES AND BUSHES ARE
 DISTANCED FROM WATER METERS AND BACKFLOW ASSEMBLIES,
 AND PROVIDED UPDATED LANDSCAPING PLAN SHOWING THE
 REVISED METER AND BACKFLOW LOCATIONS.
 -ENSURE COMPLYING WITH CONDITIONS IN SITE PLAN APPROVAL
 LETTER ISSUED BY WPB PLANNING, INCLUDING THOSE
 REGARDING IRRIGATION.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SYSTEM SUCH AS A WELL OR
 TANK.
 -COMMUNICATE WITH GREG MIHALKO [email protected] FROM
 WPB PARKS DEPARTMENT CONCERNING THE PPRC IRRIGATION
 CONDITIONS AS THE EXISTING METER AND BACKFLOW PROPOSED
 TO BE RELOCATED IS FOR PARKS IRRIGATION. VERIFY HIS
 APPROVAL AND INDICATE WHAT HIS DIRECTIONS ARE. ALSO
 INDICATE IF ANOTHER METERED WATER SERVICE IS NEEDED, OR
 IF PRIVATE IRRIGATION WILL RUN OFF 3 INCH DOMESTIC
 METER.
 -PLANS REFERENCE IRRIGATION PLANS. ADD COPY OF
 IRRIGATION PLANS IN RESUBMITTAL PACKAGE.
  
 COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 1. ON EVERY SHEET WITH ELEVATION INFORMATION, LIST THE
 VERTICAL DATUM AND PROVIDE THE CONVERSION EQUATION TO
 NGVD1929.
 2. INDICATE WHERE PROPOSED EAST PROPERTY LINE IS
 DETERMINED BY DIMENSIONING THE NORTH AND SOUTH PROPERTY
 LINES AND/OR DIMENSION FROM THE RAILROAD RIGHT OF WAY
 LINE.
 3. PROVIDE CROSS SECTIONS FOR THE CLEMATIS ST AND
 QUADRILLE PLAZA DRIVE FRONTAGES FROM THE FACE OF THE
 BUILDING (PREFERABLY AT A DOOR OPENING) TO BEYOND THE
 CURB OR GUTTER. LABEL THE BUILDING LINE, R/W OR
 PROPERTY LINE, NAME OF THE R/W, SIDEWALKS,
 CURBS/GUTTERS, LANDSCAPING, PARKING, ETC. SHOW SURFACE
 BREAKS AND SURFACE SLOPES (AS PERCENTAGES). THE
 SIDEWALK IS NOT TO GO UP AND DOWN TO MEET THE DOOR
 OPENINGS ALONG THE BUILDING FRONTAGE. SHOW EXISTING
 CONDITIONS ON THE SECTIONS.
 4. HATCH ANY SIDEWALKS TO BE REPLACED WITHIN THE RIGHT
 OF WAY.
 5. LABEL THE SIZE AND MATERIAL OF ALL UTILITIES WITHIN
 THE RIGHT OF WAY.
 6. PROVIDE THE EXISTING INVERT AND RIM ELEVATIONS FOR
 THE EXISTING DRAINAGE STRUCTURE THAT IS BEING CONNECTED
 TO WITH THE ONSITE DRAINAGE SYSTEM.
 7. HOW WILL THE 1-FOOT SPACE BETWEEN THE BUILDINGS
 DRAIN?
 8. HOW WILL THE AREA CONNECTED TO THE WEST DRIVEWAY IN
 THE ALLEY DRAIN?
 9. COMPLETE THE DRAINAGE DESIGN. PROVIDE INVERT
 ELEVATIONS FOR THE 15??? RCP PIPE IN PLAN VIEW AND ON
 THE A3-C.S. DETAIL. R-TANK SYSTEM DETAILS HAVE NOTES
 STATING ??????SIZE TO BE DETERMINED DURING FINAL
 DESIGN??? AND ???10-INCH MAINTENANCE PORT (TYPICAL
 LOCATIONS TO BE VERIFIED BY ENGINEER)???.
 10. LABEL THE TOP AND BOTTOM ELEVATIONS OF THE R-TANK
 SYSTEM.
 11. DETAIL FOR A3-C.S. SHOWS ALL CONNECTING PIPES TO BE
 RCP. SITE DEVELOPMENT PLAN ONLY SHOWS THE OUTFALL PIPE
 AS RCP AND THE OTHER PIPES AS HDPE.
 12. REVISE THE TYPICAL PARKING SPACES DETAIL TO MATCH
 THE CITY???S LAYOUT IN SECTION 94-485 OF THE CITY???S
 CODE OF ORDINANCES. THERE IS 12 INCHES OF OPEN SPACE
 BETWEEN THE PARALLEL 4-INCH STRIPES AND THE ENDS OF THE
 PARALLEL STRIPES ARE CONNECTED WITH A 4-INCH STRIPE.
 13. INCLUDE THE CITY???S STANDARD DETAIL FOR TRENCH
 BACKFILL PAVEMENT RESTORATION.
 14. PROVIDE A DETAIL FOR INLET PROTECTION ON THE
 POLLUTION PREVENTION PLAN. THE PPP APPEARS TO SHOW
 USING STAKED SILT FENCE.
 15. NOTE ON THE LEFT SIDE OF THE PPP IS CUTOFF.
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 -UNUSED SERVICE/METER ON NORTH END OF PROJECT WILL NEED
 TO BE REMOVED. (CUT AND CAP AT MAIN)
 -DIRECTION OF FLOW NOT SHOWN FOR PROPOSED SANITARY
 SEWER LATERAL
 -PROVIDE A PROFILE FOR SANITARY SEWER LATERAL FROM
 MANHOLE UP TO PROPERTY LINE. (THE APPROPRIATE CLEARANCE
 BETWEEN PROPOSED LATERAL AND EXISTING WM DOESN???T
 APPEAR TO BE MET).
 -CALL OUT PROPOSED MANHOLE AS ???DOGHOUSE??? MANHOLE
 -8??? CLEANOUT WILL BE REQUIRED FOR PROPOSED LATERAL
 (WILL SERVE AS CITY???S POINT OF SERVICE)
 -GREASE TRAP CONNECTION IS UNCLEAR, PLEASE SPECIFY
 (WILL CONNECTION BE MADE TO PROPOSED LATERAL OR
 EXISTING MAIN?)
 -6??? GATE VALVE FOR PROPOSED FIRE LINE WILL SERVE AS
 CITY???S POINT OF SERVICE, AN EASEMENT WOULD BE NEEDED
 IN THE PROPOSED LOCATION
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***