Plan Review Details - Project E23010020
Plan Review Stops For Project E23010020
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 2 Status F Date 06-09-2023 Cont ID  
Sent By lquinone Date 06-09-2023 Time 15:52 Rev Time 0.00
Received By lquinone Date 06-09-2023 Time 15:52 Sent To  
Notes
2023-06-09 15:53:00E23010020 - SUNVIEW MEDICAL CENTER - 1041 45TH ST.
 RESUB 4.24.23
  
 NO COMMENTS FROM LINDA QUI??ONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES DEPT., 561-494-1085
 [email protected] :
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -PEAK WATER DEMAND WAS LISTED AT 143GPM. 2??? BADGER
 M170 METER WOULD BE USED FOR THIS APPLICATION, AND IT
 CANNOT BE USED IF FLOW WILL EXCEED 100GPM FOR 60
 MINUTES. PLEASE VERIFY FLOW WILL NOT EXCEED 100GPM FOR
 60 MINUTES AT ANY TIME.
  
 -POLY PIPE CANNOT BE USED BETWEEN METER AND BACKFLOW
 ASSEMBLY. CONSIDER REVISING LABEL FOR PIPING TO COMPLY
 WITH DETAIL WS1 AND WS6. (THOSE SHOW THE NECESSARY PIPE
 MATERIAL, REQUIRED DEPTH, AND REQUIRED SLEEVING)
  
 -DEMOLITION PLANS LABEL EXISTING WATER METER AS 2???,
 BUT IT IS CURRENTLY 3??? SIZE.
  
 NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
 NO COMMENTS IN PREVIOUS SUBMITTAL
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 -CITY RECORDS SHOW EXISTENCE OF SECOND WATER SERVICE
 CONNECTION FOR THIS PROPERTY. PLEASE VERIFY AND
 ELABORATE ON WHAT IS TO HAPPEN TO THIS SERVICE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 03-24-2023 Cont ID  
Sent By lquinone Date 03-24-2023 Time 07:55 Rev Time 0.00
Received By lquinone Date 03-24-2023 Time 07:55 Sent To  
Notes
2023-03-24 07:55:28E23010020 - SUNVIEW MEDICAL CENTER - 1041 45TH ST.
 FIRST SUB
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 1. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 2. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 3. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 4. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND
 IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS,
 AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. GATE
 VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR SIDEWALK.
 ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE
 VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON
 PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPES SIZES AND
 MATERIALS, LOCATED ON THE RIGHT-OF-WAY.
 5. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS,
 INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITY WATER METERS.
 6. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND
 EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS
 SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF
 EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS
 SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY
 LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED
 ABOVE-GROUND ONLY.
 7. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER (IF ANY) AS DCDA. SPECIFY
 LEAD FREE DESIGN ON ALL BACKFLOWS.
 8. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING
 AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR
 GREATER.
 9. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 10. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES AT ALL UTILITY CROSSINGS WITHIN ROW PER
 CITY OF WEST PALM BEACH STANDARD DETAIL GN-2 SERIES.
 PLEASE SHOW ALL EXISTING AND PROPOSED UNDERGROUND
 UTILITY LAYOUT, INCLUDING FIBER OPTIC, ELECTRIC, GAS,
 AND CABLEVISION & TELECOMMUNICATION FACILITIES WITH
 PIPE MATERIAL AND SIZE, LOCATED ON THE RIGHT-OF-WAY.
 11. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE
 PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW
 DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING
 USC APPROVED LEAD-FREE DESIGN.
 12. PLEASE CLEARLY SHOW ROAD RIGHT OF WAY.
 13. IF TRENCHING IN IN CITY-MAINTAINED ROADWAY AREAS
 ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION
 TRANSITION ON EACH SIDE OF PROPOSED TRENCH PER CITY OF
 WPB STANDARD DETAIL GC-4.
 14. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 15. COORDINATE WITH PALM BEACH COUNTY FOR WORK IN THEIR
 RIGHT OF WAY.
 16. PLEASE CONFIRM THAT PLANNING REVIEWED PROPOSED SITE
 REVISIONS.
 17. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX).
  
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -CLEARLY SHOW AND LABEL SOUTH PROPERTY LINE.
 -FIRELINE BACKFLOW ASSEMBLY IS LEAKING AND NEEDS
 REPAIR.
 -CANNOT FIND WATER AND SEWER DEMAND CALCULATIONS ON
 SHEET C400.
 -ON LABEL OF PROPOSED BACKFLOW PREVENTER, REVISE
 WORDING TO RP BACKFLOW ASSEMBLY AND ADD SIZE OF
 BACKFLOW ASSEMBLY.
 -WHY IS ANOTHER METERED WATER SERVICE NEEDED? WHAT WILL
 IT BE FEEDING?
 -VERIFY PROPOSED 2 INCH METER WILL NOT FEED FIRE
 SPRINKLERS.
 -IF PROPOSED 2 INCH METER ON PRIVATE PROPERTY, THEN
 SHOW AND LABEL UTILITY EASEMENT. (MAY HELP TO PROVIDE
 BLOWUP DETAIL.
 -PROPOSED BACKFLOW ASSEMBLY SHOULD NOT BE IN RIGHT OF
 WAY. ADJUST LOCATION IF NEEDED.
 -ADD MARKUP NOTE TO STANDARD DETAIL WS1 THAT DUAL CHECK
 VALVE IS NOT USED WHEN A BACKFLOW ASSEMBLY IS BEING
 INSTALLED.
 -SHOW SAMPLE POINT IF NEEDED OR REQUIRED.
 -LABEL WATER MAIN AND WATER SERVICE WITH PIPE SIZE AND
 MATERIAL TYPE.
  
 NO COMMENTS FROM TRACY WARD, SR. STORMWATER ENG.,
 ENGINEERING SERVICES, [email protected] 561-494-1120:
  
 COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
  
 -LABEL SIZE AND MATERIAL OF EXISTING WATER MAIN
 -SHOW ALL DRY UTILITIES ON PLAN VIEW
 -MAKE PROPERTY LINE MORE APPARENT
 -SHOW EXISTING FIRE HYDRANT ON EAST SIDE OF PROJECT, AS
 WELL AS CORRECT ALIGNMENT OF EXISTING FIRELINE
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***