| 2022-12-16 09:13:45 | E21120012 - ROYAL POINCIANA PLAYHOUSE INITIAL REVIEW |
| | 12.15.22 |
| | |
| | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | 1. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 2. SHOW EXISTING EASEMENTS FOR EXISTING WM. |
| | 3. LABEL EXISTING SOURCE OF WATER ON ROYAL POINCIANA |
| | WAY (PIPE SIZE & MATERIAL, METER, ETC.) |
| | 4. SHOW MASTER METER AT ROW (IF EXISTING). |
| | 5. NEED CONFIRMATION FROM CITY OF WPB PUB. UTILITIES |
| | CUSTOMER SERVICE IF ONSITE LINE IS PUBLIC OR PRIVATE. |
| | 6. PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, GREASE TRAPS, ETC. INCLUDING |
| | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY |
| | SEWERS, THE MAKE AND MODEL OF ALL VALVES, POTABLE AND |
| | IRRIGATION METERS, BACKFLOWS, FIRE HYDRANTS AND FDCS, |
| | AND OTHER DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH |
| | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES |
| | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, |
| | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND |
| | MANHOLES AND PROFILES OF SANITARY SEWER LINES. |
| | 7. PLEASE SHOW EXISTING AND PROPOSED UTILITY EASEMENTS, |
| | INCLUDING THOSE PROPOSED TO ALLOW ACCESS FOR CITY |
| | PERSONNEL TO PROPOSED UTILITY WATER METERS. |
| | 8. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION, AND |
| | EXISTING METER AND BACKFLOW (TO BE REMOVED?). BACKFLOWS |
| | SHALL BE INSTALLED ON PRIVATE PROPERTY OUTSIDE OF |
| | EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER METERS |
| | SHALL BE INSTALLED IMMEDIATELY ADJACENT TO PROPERTY |
| | LINE. 3 INCH AND LARGER WATER METERS SHALL BE INSTALLED |
| | ABOVE-GROUND ONLY. |
| | 9. ENGINEERING PLANS SHALL INCLUDE PIGGING, FLUSHING |
| | AND SAMPLE POINTS ON ANY WATER RUNS 60 FT. IN LENGTH OR |
| | GREATER. |
| | 10. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES AT ALL UTILITY CROSSINGS PER CITY OF |
| | WEST PALM BEACH STANDARD DETAIL GN-2 SERIES. |
| | 11. WHEN SUBMITTING APPROVED MATERIALS LIST, PLEASE |
| | PROVIDE MATERIAL/CUT SHEETS FOR ALL PROPOSED BACKFLOW |
| | DEVICES SHOWING SPECIFIC MODEL NUMBER AND SPECIFYING |
| | USC APPROVED LEAD-FREE DESIGN. |
| | 12. PLEASE CLEARLY LABEL ROAD RIGHT OF WAY. |
| | 13. PLEASE PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | 14. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (E-XXXXXXXX). |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | |
| | -CLEARLY SHOW AND LABEL METERED WATER SERVICE FOR 150 |
| | ROYAL POINCIANA PLZ |
| | -CLEARLY SHOW AND LABEL PROPERTY LINES FOR 150 ROYAL |
| | POINCIANA PLZ. |
| | -ADD COPY OF SURVEY TO RESUBMITTAL PACKAGE. |
| | -ADD COPY OF ANY LANDSCAPING PLAN TO RESUBMITTAL |
| | PACKAGE, AND ENSURE LANDSCAPING IS DISTANCED FROM WATER |
| | METERS AND BACKFLOW ASSEMBLIES. |
| | -DDCV ON SHEET 10 IS EXCESSIVELY FAR FROM WATER MAIN. |
| | RELOCATE MUCH CLOSER TO WATER MAIN, BUT NOT IN ANY |
| | UTILITY EASEMENTS. |
| | -FOR THE FIRELINE ON SHEET 10: WHAT DOES IT SERVICE; |
| | WHY IS IT ENTERING THE SMALL BUILDING WITH THE CHILLER |
| | -VERIFY THE PRIVATE FIRE SYSTEMS WILL NOT HAVE ADDED |
| | CHEMICALS AND WILL NOT BE CONNECTED TO AN AUXILIARY |
| | WATER SYSTEM SUCH AS A WELL. |
| | -PROVIDE SIGNED AND SEALED FLOW CALCULATIONS FOR EACH |
| | FIRELINE AS DIRECTED IN WS5 NOTE 9. |
| | -LABEL ALL EXISTING WATER MAIN SEGMENTS WITH PIPE SIZE |
| | AND MATERIAL TYPE. |
| | -SHOW AND LABEL ALL EXISTING AND PROPOSED UTILITY |
| | EASEMENTS. |
| | -PLAN SHOWS WATER METER AND BACKFLOW SLIGHTLY NORTH OF |
| | PROPOSED 3 INCH FIRELINE ON SHEET 10. CANNOT SEE IT IN |
| | HISTORIC PICTURES OF AREA. VERIFY IF STILL THERE AND |
| | LABEL IF PROPOSED. |
| | -ADD PROPERTY AND BUILDING ADDRESSES. |
| | -UTILITY BILLING SYSTEM SHOWS EXISTING 6 INCH FIRELINE |
| | AT 70 ROYAL POINCIANA PLZ. PLEASE SHOW AND LABEL ON |
| | PLANS. |
| | -COULD NOT FIND WATER AND SEWER DEMAND CALCULATIONS ON |
| | WATER PLANS. |
| | -IS THE 2 INCH CHILLER LINE PROPOSED TO BE FED BY THE |
| | PROPOSED 1.5 INCH METERED WATER SERVICE? IF SO, VERIFY |
| | SERVICE LINE AND METER SIZE ARE SUFFICIENT. |
| | -RELOCATE BACKFLOWS AND WATER METERS SHOWN ON SHEET 11 |
| | MUCH CLOSER TO WATER MAIN. MAKE SURE THEY ARE NOT |
| | ENCROACHING ON NEIGHBORING PROPERTY AND NOT ON TOP OF |
| | FPL UTILITY. BACKFLOW ASSEMBLIES SHOULD NOT BE IN ANY |
| | UTILITY EASEMENTS. |
| | -IF ANY FDC ARE NEEDED OR REQUIRED, SHOW AND LABEL ON |
| | PLANS. |
| | -ENSURE METERS AND BACKFLOWS ARE NOT PROPOSED TOO CLOSE |
| | TO POLES AND SIGNS. |
| | -ADD MARKUP NOTE ON WS1 THAT DUAL CHECKS ARE NOT USED |
| | WHEN BACKFLOW ASSEMBLIES ARE INSTALLED. |
| | -ADD STANDARD DETAIL WS2 TO SHEET 12. |
| | |
| | COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS |
| | EXAMINER, [email protected], 561-494-1101: |
| | |
| | -LIST THE SIZE AND MATERIAL OF THE SERVICES BEING |
| | REMOVED, AS WELL AS THEIR BACKFLOWS AND METERS |
| | -POINTS OF SERVICE NEED TO BE CALLED OUT |
| | -PROPOSED 3??? FIRE LINE NEEDS TO HAVE MATERIAL LISTED |
| | -CROSSING INFO NEEDED BETWEEN 3 INCH FIRE LINE AND |
| | EXISTING TELEPHONE CONDUIT |
| | -PROVIDE A PROFILE FOR THE 3 INCH FIRE LINE |
| | -PROVIDE WATER DEMAND CALCULATIONS FOR EXISTING AND |
| | PROPOSED CONDITIONS |
| | -ADD DATUM CONVERSION |
| | -SEPARATE TAPS REQUIRED FOR FIRE LINE AND POTABLE LINE |
| | PER DETAILS WS-1 AND WS-4 |
| | -HORIZONTAL SEPARATION BETWEEN PROPOSED WATER LINE AND |
| | FPL LINE ON SOUTHERN END OF PROJECT IS NOT TO STANDARD |
| | -WATER MAIN MUST BE DIP PER STANDARDS (NOT PVC) |
| | |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT (561) 494-1098 [email protected] |
| | |
| | |