Plan Review Details - Project E17110002
Plan Review Stops For Project E17110002
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 01-03-2018 Cont ID  
Sent By squinone Date 01-03-2018 Time   Rev Time 0.00
Received By squinone Date 12-20-2017 Time   Sent To  
Notes
2018-01-03 11:44:29PROJECT: THE CRYSTAL, E17110002
 LOCATION ADDRESS: 3611 SOUTH FLAGLER DRIVE
 STATUS: FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 GENERAL COMMENTS:
 1. FDEP FORMS NEEDS TO BE SIGNED BY THE EOR PRIOR TO
 CITY'S SIGNATURE.
 2. REVIEW NEW FEMA FIRM MAPS. TWO FEET OF FREEBOARD
 ABOVE BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL
 FLOOD HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE
 AVAILABLE: HTTP://MAPS.CO.PALM-BEACH.FL.US/CWGIS/MYGEON
 AV.HTML?APP=FLOODZONES
 3. MISSING COVER SHEET, SHEET INDEX, VICINITY MAP, ETC.
 REFER TO PLAN SUBMITTAL CHECKLIST IN THE DEVELOPMENT
 APPROVAL APPLICATION: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 COMMENTS FOR SHEET C01:
 1. ADD MUTCD SIGN DESIGNATION NAME.
 2. MINIMUM DIMENSIONAL (E.G. THE GATE WIDTH MUST BE A
 MINIMUM OF 12.5 FEET) REQUIREMENTS FOR THE ENCLOSURE
 ARE LISTED IN CODE OF ORDINANCES, SECTION 94-444(B) OF
 THE CODE OF ORDINANCES. CITY STANDARD DETAIL GC-8 MAY
 BE DOWNLOADED AT: HTTP://WPB.ORG/ENGINEERING/ENGINEERIN
 G-SERVICES/ENGINEERING-STANDARDS/
 3. HAS THE DUMPSTER LOCATION AND DIMENSION BEEN
 APPROVED BY PETER BIENIEK, PUBLIC WORKS DIRECTOR?
 4. REFER TO CITY STANDARD DETAIL GC-6 FOR CONCRETE
 DRIVEWAY APRONS, THE PLANS DOES NOT MATCH THE DETAIL
 AND 10-FEET MAX FOR TWO ENTRANCES: HTTP://WPB.ORG/ENGIN
 EERING/ENGINEERING-SERVICES/ENGINEERING-STANDARDS/
 5. SIDEWALK WITHIN THE DRIVEWAY LIMITS MUST BE REPLACED
 TO 6-INCH THICK, 3000 PSI. REFER TO CITY STANDARD
 DETAIL GC-6.
  
 COMMENTS FOR SHEET C02:
 1. TEXT SHOULD BE READ FROM THE RIGHT HAND SIDE (EG.
 SOUTH FLAGLER DRIVE AND EX. CONCRETE WALK SHOULD BE
 ROTATED).
 2. ADD LF FOR PROPOSED PIPES.
 3. SHOW ALL UTILITY CONFLICT DETAIL FOR ONSITE.
 4. SHOW DIRECTION OF FLOW FOR THE EXISTING SANITARY
 SEWER. SHOW INVERT AT CONNECTION POINTS AND INCLUDE A
 PROFILE FOR THE PROPOSED SERVICE LATERAL WITH GROUND
 ELEVATIONS ABOVE THE PIPE;
 5. ENGINEER OF RECORD MUST SUPPLY FLOW CALCULATIONS TO
 ESTABLISH ACCEPTABLE WATER VOLUME AND PRESSURE FROM THE
 WATER MAIN TO THE BUSINESS. SUBMIT CALCULATIONS TO
 VALIDATE METER SIZE SELECTION. SUCH CALCULATIONS MUST
 BE SIGNED AND SEALED BY STATE OF FLORIDA LICENSED
 ENGINEER. SHOW ON THE PLANS.
 6. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH
 AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT
 ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED
 DEVELOPMENT. SHOW ON THE PLANS.
 7. SHOW EXISTING 8-INCH PVC SANITARY SEWER PIPE.
 LOCATION OF EXISTING SANITARY SEWER MIGHT CONFLICT WITH
 PROPOSED LOCATION OF 8-INCH DIP WATERMAIN.
 8. CHANGE 'DOMESTIC BACKFLOW' TO 'REDUCED PRESSURE
 PREVENTER ASSEMBLY (RPPA)'.
 9. POOL AREA REQUIRES WATER AND SEWER SERVICES. PLEASE
 SHOW PROJECTED DEMANDS ON THE UTILITY PLAN SHEET.
 10. INCLUDE 4-INCH GATE VALVE AFTER THE WATER METER AS
 CITY'S POINT OF SERVICE.
 11. SHOW METER SIZE.
 12. UPDATE UTILITY LEGEND FROM 'PROPOSED SEWER SERVICE'
 TO 'PROPOSED STORM SEWER SERVICE'.
  
 COMMENTS FOR SHEET C05:
 1. CHANGE 'ASPHALT PAVEMENT DETAIL' TO 'ASPHALT
 PAVEMENT DETAIL (ONSITE)'.
  
 COMMENTS FOR SHEET EC-1:
 1. MAINTENANCE INSPECTION PROCEDURE NOTE 3 MUST REFER
 TO CITY STANDARD DETAIL PC-2 NOTE 4.
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved