Plan Review Details - Project E16090007
Plan Review Stops For Project E16090007
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status   Date 09-14-2016 Cont ID  
Sent By   Date 09-15-2016 Time   Rev Time 4.00
Received By   Date 09-14-2016 Time   Sent To  
Notes
2016-09-14 16:01:38FOLLOWING ARE THE COMMENTS ON WATER AND SEWER PLAN
 (SHEET C-8):
 1. PROPOSED SANITARY MANHOLE MH-1 IS PLACED ON THE
 PROPERTY LINE. MOVE IT ON SITE I.E. WITHIN THE PROPERTY
 LINE (REFER TO #1 COMMENT ON THE ATTACHED MARKED-UP
 SHEET).
 2. PLAN SHOWS TWO (2) 90? BENDS THOSE ARE PROPOSED FOR
 A NEW 8IN. WATER MAIN TO CONNECT TO AN EXISTING 8IN. WM
 STUB TO AVOID A STORM DRAIN MANHOLE (REFER TO THE AREA
 NEAR THE 1-1/2IN. WATER METER WITH 1-1/2IN. BACKFLOW
 PREVENTER ASSEMBLY, REFER TO #2 ON THE ATTACHED
 MARKED-UP PLAN).). THE CITY WILL NOT ACCEPT FITTINGS
 FOR WATER MAIN WHILE INSIDE THE RIGHT-OF-WAY (UP THE
 GROVE LANE). USE 2IN. POLY OR COPPER FROM THE 8IN. STUB
 OUT (REFER TO CITY?S STANDARD DETAIL WS-1, ISSUED IN
 2016). ALSO SHOW VERTICAL CONFLICT ELEVATIONS WITH THE
 STORM DRAIN WHILE CROSSING.
 3. UTILITY EASEMENT WILL BE REQUIRED FOR THE PROPOSED
 WATER METER ONSITE (REFER TO THE SKETCH LABELED #10 ON
 THE ATTACHED MARKED-UP PLAN).
 4. REMOVE THE 8IN. PVC SANITARY PIPE STUB/PLUG IT FROM
 INSIDE THE EXISTING MANHOLE LOCATED ON UP THE GROVE
 LANE (REFER TO #3 ON THE ATTACHED MARKED-UP PLAN).
 PLACE A NOTE ON THE PLAN: ?REHABILITATE MANHOLE PER
 CITY STANDARD?.
 5. 2IN. AND 4IN. PVC CONDUITS ARE SHOWN CROSSING THE
 2-IN. AND 6IN. WATERLINES. FROM THE CIVIL PLANS IT IS
 NOT CLEAR WHERE ARE THEY GOING. PLEASE SHOW CONFLICT
 WITH THE EXISTING 15IN. STORM DRAINS (ON UP THE GROVE
 LANE) IF THEY ARE CROSSING OVER INSIDE THE STREET
 RIGHT-OF-WAY (REFER TO #4 ON THE ATTACHED MARKED-UP
 PLAN). A PRIVATE UTILITY EASEMENT WILL BE REQUIRED IF
 CONDUITS GO OUT ON THE CITY RIGHT-OF-WAY.
 6. EXISTING DRIVEWAYS APRON/ENTRANCE TO THE EXISTING
 ROCK AREA SHALL BE REMOVED (REFER TO #5 ON THE ATTACHED
 MARKED-UP PLAN). PUT A LABEL ON THE PLAN NOTING:
 ?DRIVEWAY APPROACH SHALL BE REMOVED AND RESTORE WITH
 GRASS?
 7. LABEL SIZE AND MATERIAL FOR THE EXISTING WATERLINE
 THAT IS CONNECTING THE EXISTING 6IN. DDCV AND THE
 1-1/2IN. IRRIGATION METER TO THE EXISTING 10IN. DIP WM
 TO THE SOUTH (REFER TO #6 ON THE ATTACHED MARKED-UP
 PLAN).
 8. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT IN.ALL BACKFLOW DEVICES
 MUST BE LEAD FREE.IN. FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 9. NEAREST FIRE DEPARTMENT CONNECTION (FDC) DISTANCE TO
 FIRE HYDRANT SHALL BE A MAXIMUM OF 150 LINEAR FEET.
 CONSULT MEP AND FIRE CODE TO VERIFY (REFER TO #8 ON THE
 ATTACHED MARKED-UP PLAN).
 10. PLEASE USE THE CITY'S LATEST DETAILS FOR THE
 FOLLOWING STANDARD DETAILS: WS-1; WS-5; P-3.
  
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status P Date 10-27-2016 Cont ID  
Sent By   Date 10-27-2016 Time 3:30 Rev Time 2.00
Received By   Date 10-25-2016 Time 4:00 Sent To  
Notes
2016-10-27 15:40:34PLAN REVIEW FOR THIS PROJECT. IS NOW COMPLETE AND
 CITY'S UTILITY ENGINEER, LAURA LE, WILL SIGN OFF ON IT
 TOMORROW MORNING (ALONG WITH THE THE WATER PERMIT:
 PBCHD ECR II 12(2)A). ONCE SHE SIGNS OFF ON IT WE WILL
 HAVE TWO SETS OF APPROVED/STAMPED PLANS FOR YOU TO PICK
 UP FROM OUR DEPARTMENT. I WILL SEND THE FINAL INVOICE
 (FOR THE REMAINING BALANCE FOR DEVELOPMENT REVIEW AND
 CONSTRUCTION ADMIN FEES) IN A SEPARATE EMAIL SHORTLY.
 NEXT STEP IN THE PROCESS WOULD BE A PRE-CONSTRUCTION
 MEETING PRIOR TO CONSTRUCTION PROVIDED OTHER PERMITS
 HAVE BEEN OBTAINED FROM DIFFERENT CITY DEPARTMENTS.
 PLEASE SEND ME A LIST OF PEOPLE WHO YOU WANT TO BE
 INVITED IN THE PRE-CON. IF YOU HAVE ANY QUESTIONS OR
 COMMENTS PLEASE DO NOT HESITATE TO CONTACT ME.

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***