Plan Review Details - Project E15110026
Plan Review Stops For Project E15110026
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status P Date 01-21-2016 Cont ID  
Sent By mgonzale Date 01-21-2016 Time 08:41 Rev Time  
Received By mgonzale Date 11-13-2015 Time   Sent To  
Notes
2016-01-21 08:22:15COMMENTS: ALL COMMENTS BELOW HAVE BEEN ADDRESSED.
  
 #1 PROJECT REQUIRES ALL PAVEMENT MARKING IN ROW TO BE
 CALLED OUT AS THERMOPLASTIC.
  
 #2 CROSSING AT WEBSTER AND BUNKER INTERSECTION MUST
 HAVE THE 12 INCH WIDE DOUBLE LINES PEDESTRIAN CROSSING.
  
 #3 CALLOUT FDC (FIRE DEPARTMENT CONNECTION) ON PLAN.
 NOTE DCDA (FIRE BACKFLOW) SHALL BE LEAD FREE. THE RPPA
 (DOMESTIC WATER BACKFLOW SHALL ALSO BE CHECKED TO SEE
 IF IT COMPLIES WITH "LEAD FREE" COMPLIANCE. AS OF
 DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT
 TP://WPB.ORG/WP-CONTENT/UPLOADS/2015/12/CROSS-CONNECTIO
 N-MANUAL.PDF
  
 #4 WEBSTER AVENUE SHALL BECOME A STANDARD 24 FOOT WIDE
 ROAD WITH THE MINIMUM RADIUS OF 20 FEET. THIS WILL
 ALLOW ENOUGH ROOM FOR ADA RAMPS AT INTERSECTION
 CROSSING.
 IT SHALL HAVE 5 FOOT SIDEWALKS MINIMUM WITH A 6 INCH
 TYPE F-CURB REVEAL.
  
 #6 HATCH PATTERN AT DRIVEWAY APRON EXITING TO BUNKER
 ROAD IS MISSING. IT SHALL BE OF CONCRETE MATERIAL 4000
 PSI MINIMUM 6 INCHES THICK.
  
 #7 4 INCH DIAMETER WATER MAIN STUB SHALL BE CUT IN BACK
 AT THE MAIN AND NOTED AS SUCH WITH CAP AND RESTRAINED.
  
 #8 INSTALL A CLEAN OUT FOR EXISTING SEWER LATERAL IN
 GRASS MEDIAN LOCATION, SHOW A CONCRETE COLLAR ON
 CLEAN-OUT.
  
 #9 AT THE PROPOSED 6 INCH DIAMETER PVC SEWER LATERAL
 CALL OUT AS PVC SDR 26 MATERIAL.
  
 #10 FIRELINE DEDICATED SHALL HAVE A FOUR-INCH RESIDENT
 WEDGE GATE VALVE JUST INSIDE THE PROPERTY IN A UTILITY
 EASEMENT.
  
 #11 FIRELINE INSTALL WILL CONFLICT WITH EXISTING TREE.
 MAKE A NOTATION IF TREE REMAINS OR IF IT WILL BE
 REMOVED.
  
 #12 AT SE CORNER THERE ARE TWO POLES IN THE SIDEWALK,
 ONLY ONE IS SHOWN IN YOUR PLAN. COULD YOU SHOW BOTH SO
 THAT THE PLAN CAN BETTER DETERMINE THE ADA ROOM
 REQUIRED FOR THE PEDESTRIAN RAMPS.
  
 #13 WHERE A SECTION DETAIL IS SHOWN, PLEASE NOTE WHAT
 SHEET NUMBER OF PLAN VIEW IT WAS TAKEN FROM.
  
 #14 SECTION GG REFERENCES SHEET C5 HOWEVER IT IS SHOWN
 ON SHEET C6, PLEASE CHECK OTHERS.
  
 #15 THE HANDICAP DETAIL SHOWING ON C3 IS NOT A CITY
 STANDARD DETAIL. DIMENSIONS ARE DIFFERENT OF THOSE IN
 OUR CITY STANDARD, EXAMPLE THE WHEEL STOPS SHOW A 2.5
 FOOT DIMENSION AT CAR STOP, THAT SHOULD BE 2 FEET.
 CHECK FOR OTHER INCONSISTENCIES.
  
 #16 SECTION HH ON SHEET C1 SHOWS A TYPE OF CURB;
 HOWEVER, THE SECTIONAL DETAIL SHOWS A TYPE D CURB.
  
 #17 LARGE SECTION CALL OUT ON C3 IS REFERENCING SHEET
 C2.
  
 #18 NO PARKING LIGHT POLES ARE SHOWING ON PLAN VIEW,
 PLEASE SHOW TO AVOID POTENTIAL CONFLICTS WITH OTHER
 ELEMENTS.
  
 #19 ON SHEET C5 AT NEW 20 FOOT RADIUS CURBS IT IS
 SUGGESTED TO SHOW A DRAINAGE FLUME OPENING TO AVOID
 PONDING AT INTERSECTION. GRASSED MEDIANS NEAR THESE
 FLUMES SHALL BE GRADED TO RECEIVE FLOW.
  
 #20 PLEASE DIMENSION DUMPSTER AREA ON SHEET C2. SHOW
 CITY STANDARD DUMPSTER DETAIL FOR MINIMUM DIMENSIONS.
 OPENING WIDTH MUST BE 12FEET 6INCHES.
  
 #21 PROPOSED PAVER ALLEY SHOWS PAVERS INTO SIDEWALK OF
 ON WEBSTER. APPROACH ENTRANCE SHALL BE OF CONCRETE,
 REFER TO CITY STANDARD DRIVEWAY DETAIL OR CALL ON PLAN.
  
 #22 SHOW PROOF OF ALLEY ABANDONMENT.
  
 #23 FOR ANY RESURFACE THE MINIMUM CITY STANDARD FOR
 REPAVING WOULD BE 2 INCHES OF ASPHALT AND NOT 1 INCH AS
 SHOWN.
  
 #24 CALL OUT MILL AND RESURFACE. MAKE A NOTATION THAT
 STREET LEVEL SHALL REMAIN AT SAME ELEVATION AS EXISTING
 WHEN DONE.
  
 #25 SHEET C7 IS CALLING FROM THE PB COUNTY TRAFFIC
 DETAILS ON NOTES.
  
 #26 MAKE REFERENCE ON THE PLANTHE SOURCE OF THE
 TOPOGRAPHY INFORMATION. ALSO THE DATUM IT WAS TAKEN
 FROM. IF YOU HAVE A SURVEY OBTAINED FROM A THRID PARTY
 PLEASE SUPPLY WITH YOUR NEXT RESUBMITTAL. IDENTIFY
 ELEVARION DATUM ON EVERY SHEET WHERE TOPO IS SHOWN.
 THIS WILL ASSIST DURING AS-BUILT PHASE.
  
 #27 BLOW-OFF DETAIL SHOWN ON THE SHEET NINE IS NOT A
 CITY STANDARD DETAIL. IF YOU WANT TO USE ON-SITE THEN
 NOTE IT.
  
 #28 COULD YOU SHOW ON SITE DATA ON SHEET C-7 THE
 OFFSITE PARKING LOST PERVIOUS AND IMPERVIOUS DATA.
  
 #29 AIR RELEASE VALVE SHOWN ON SHEET 10 IS NOT
 REQUIRED, TYPICAL MANHOLE DETAIL IS NOT REQUIRED IN
 SHEET 12, THE AIR RELEASE VALVE NOT NEEDED, LARGE METER
 DETAIL NOT NEEDED. LARGE BACKFLOW DETAIL NOT NEEDED..
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE:
  
  
  
  
  
  
  
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status P Date 02-29-2016 Cont ID  
Sent By Mgonzale Date 02-29-2016 Time   Rev Time 36.00
Received By mgonzale Date 02-05-2016 Time   Sent To I
Notes
2016-02-29 14:52:20PLAN REVIEW SATISFACTORY.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***