Plan Review Details - Project E15100033
Plan Review Stops For Project E15100033
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 04-25-2016 Cont ID  
Sent By MGONZALE Date 04-25-2016 Time   Rev Time 4.00
Received By mgonzale Date 03-25-2016 Time   Sent To I
Notes
2016-04-25 11:09:06COMMENTS:
  
 #1 SEWER SERVICES NOT NEEDED SHALL BE CUT AND CAPPED AT
 THE MAIN SEWER LINE. ABANDONED MANHOLES SHALL HAVE THE
 TOP REMOVED AND GROUT FILLED.
  
 #2 METERS AND FIRELINE SHALL BE LOCATED AT THE ROW OR
 NEAR PROPERTY LINE (IF DOMESTIC METER OR FIRELINE RW
 GATE VALVE FALLS JUST INSIDE PROPERTY A UTILITY
 EASEMENT SHALL BE RECORDED ON BEHALF OF THE CITY.
  
 #3 IDENTIFY CONFLICT BETWEEN WATER AND SEWER AT TAP ON
 DATURA.
  
 #4 IDENTIFY ON SHEET C400 WHAT THE SOURCE OF THE SEWER
 WILL BE COMING FROM GARAGE.
  
 #5 IDENTIFY ON SHEET C400 TIME AND DATE OF FIRE HYDRANT
 FLOW TEST AND WHO PERFORMED THE TEST.
  
 #6 GRAVITY SEWER SHALL HAVE A CLEAN-OUT AT THE BACK OF
 SIDEWALK. THIS WOULD IDENTIFY THE CITY'S POINT OF
 SERVICE.
  
 #7 IDENTIFY 4" METER TO BE INSTALLED IN A 4 FOOT X
 6FOOT CONCRETE VAULT. CONTRACTOR TO SUBMIT SHOP
 DRAWINGS. LIDS SHALL BE ALUMINUM H-20 RATED AND SPRING
 LOAD ASSISTED.
  
 #8 SHOW EXTENTS OF MILL AND RESURFACE AT ROW WHERE WORK
 IS REQUIRED. 50 FEET ON EITHER SIDE OF TRENCH SHALL BE
 THE MINIMUM AREA. WIDTH OF PAVING SHALL BE DETERMINED
 OVER THE FULL LANE WIDTH AFFECTED.
  
 #9 CALL OUT DETAIL P-6 ON SHEET C-400 AT THE TAP
 LOCATION. DETAIL IS SHOWN ON C-530.
  
 #10 A UG FIRELINE PERMIT WILL BE REQUIRED FOR PORTION
 OF FIRELINE ON-SITE.
  
 #11 ON SHEET C-400 IDENTIFY DOMESTIC BACKFLOW ON PLAN
 AS A "HORIZONTAL RPPA" DEVICE AND THE FIRE BACKFLOW AS
 "HORIZONTAL DCDA". BOTH SHALL BE CALLED OUT AS "USC
 APPROVED" AND "LEAD-FREE".
  
 #12 SEWER CONNECTION SHALL BE INSPECTED AND TELEVISED
 UPON COMPLETION SUBMITTED TO THE CITY FOR FINAL
 ACCEPTANCE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  
  
  
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***