| 2016-04-25 11:09:06 | COMMENTS: |
| | |
| | #1 SEWER SERVICES NOT NEEDED SHALL BE CUT AND CAPPED AT |
| | THE MAIN SEWER LINE. ABANDONED MANHOLES SHALL HAVE THE |
| | TOP REMOVED AND GROUT FILLED. |
| | |
| | #2 METERS AND FIRELINE SHALL BE LOCATED AT THE ROW OR |
| | NEAR PROPERTY LINE (IF DOMESTIC METER OR FIRELINE RW |
| | GATE VALVE FALLS JUST INSIDE PROPERTY A UTILITY |
| | EASEMENT SHALL BE RECORDED ON BEHALF OF THE CITY. |
| | |
| | #3 IDENTIFY CONFLICT BETWEEN WATER AND SEWER AT TAP ON |
| | DATURA. |
| | |
| | #4 IDENTIFY ON SHEET C400 WHAT THE SOURCE OF THE SEWER |
| | WILL BE COMING FROM GARAGE. |
| | |
| | #5 IDENTIFY ON SHEET C400 TIME AND DATE OF FIRE HYDRANT |
| | FLOW TEST AND WHO PERFORMED THE TEST. |
| | |
| | #6 GRAVITY SEWER SHALL HAVE A CLEAN-OUT AT THE BACK OF |
| | SIDEWALK. THIS WOULD IDENTIFY THE CITY'S POINT OF |
| | SERVICE. |
| | |
| | #7 IDENTIFY 4" METER TO BE INSTALLED IN A 4 FOOT X |
| | 6FOOT CONCRETE VAULT. CONTRACTOR TO SUBMIT SHOP |
| | DRAWINGS. LIDS SHALL BE ALUMINUM H-20 RATED AND SPRING |
| | LOAD ASSISTED. |
| | |
| | #8 SHOW EXTENTS OF MILL AND RESURFACE AT ROW WHERE WORK |
| | IS REQUIRED. 50 FEET ON EITHER SIDE OF TRENCH SHALL BE |
| | THE MINIMUM AREA. WIDTH OF PAVING SHALL BE DETERMINED |
| | OVER THE FULL LANE WIDTH AFFECTED. |
| | |
| | #9 CALL OUT DETAIL P-6 ON SHEET C-400 AT THE TAP |
| | LOCATION. DETAIL IS SHOWN ON C-530. |
| | |
| | #10 A UG FIRELINE PERMIT WILL BE REQUIRED FOR PORTION |
| | OF FIRELINE ON-SITE. |
| | |
| | #11 ON SHEET C-400 IDENTIFY DOMESTIC BACKFLOW ON PLAN |
| | AS A "HORIZONTAL RPPA" DEVICE AND THE FIRE BACKFLOW AS |
| | "HORIZONTAL DCDA". BOTH SHALL BE CALLED OUT AS "USC |
| | APPROVED" AND "LEAD-FREE". |
| | |
| | #12 SEWER CONNECTION SHALL BE INSPECTED AND TELEVISED |
| | UPON COMPLETION SUBMITTED TO THE CITY FOR FINAL |
| | ACCEPTANCE. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF |
| | WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD |
| | FREE." |
| | FOR MORE INFORMATION REFER TO THE LINK BELOW: |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | |
| | |
| | |
| | |