| 2015-05-06 10:46:41 | ENGINEERING DEVELOPMENT APPROVAL APPLICATION REVIEW |
| | CITY OF WEST PALM BEACH |
| | PUBLIC WORKS DEPARTMENT |
| | |
| | 1. PLEASE IDENTIFY THE SOURCE OF THE AS-BUILT |
| | INFORMATION UTILIZED FOR THE POTABLE WATER, SANITARY |
| | SEWER, AND STORM SEWER DESIGN. |
| | |
| | 2. INDICATE ON THE PLANS WHICH PORTIONS OF THE POTABLE |
| | WATER, SANITARY SEWER, AND STORMWATER SYSTEM WILL |
| | REMAIN PUBLICALLY OWNED AND WHICH SECTIONS WILL BE |
| | MAINTAINED BY THE APPLICANT. TYPICALLY, THE CITY'S |
| | OWNERSHIP STOPS AT THE RIGHT-OF-WAY LINE UNLESS |
| | EXTENUATING CIRCUMSTANCES REQUIRED THE OWNERSHIP |
| | DIVISION TO TAKE PLACE AT ANOTHER LOCATION. |
| | |
| | 3. PLEASE SUBMIT ONE SIGNED AND SEALED COPY OF BOTH THE |
| | LIFT STATION DESIGN CALCULATIONS AND DRAINAGE |
| | CALCULATIONS. |
| | |
| | 4. PLEASE INCLUDE A DETAIL ON THE CONSTRUCTION PLANS |
| | FOR THE PROPOSED PRIVATE LIFT STATION. |
| | |
| | 5. PLEASE VERIFY THAT THE PROPOSED NEW BUILDING WILL |
| | NOT INCLUDE FOOD PREPARATION AREAS. IF FOOD PREPARATION |
| | AREAS ARE INCLUDED, PLEASE VERIFY THAT THE DESIGN MEETS |
| | THE FLORIDA BUILDING CODE AND SECTION 90-125 OF THE |
| | CITY?S CODE OF ORDINANCES. (BUILDING DESIGN IS UNDER |
| | REVIEW BY THE RIVIERA BEACH.) |
| | |
| | 6. PLEASE INDICATE THE VERTICAL DATUM ON THE |
| | CONSTRUCTION PLANS. SECTION 78-9 OF THE CITY?S CODE OF |
| | ORDINANCES SPECIFIES NGVD 1929 AS THE OFFICIAL CITY |
| | VERTICAL DATUM. |
| | |
| | 7. PLEASE DESIGNATE RIBBON OR OTHER MOUNTABLE CURB TYPE |
| | FOR THE ENTRANCE TO THE EMERGENCY ACCESS NEAR THE NORTH |
| | EAST CORNER OF THE PARCEL. CONSIDER ADDING SIGNAGE TO |
| | INDICATE THAT THIS AREA IS FOR EMERGENCY USE ONLY AND |
| | NOT TO BE BLOCKED BY VEHICLES. |
| | |
| | 8. CONSIDER INCREASING THE SIDEWALK THICKNESS IN THE |
| | AREA WITHIN THE EMERGENCY ACCESS, JUST EAST OF THE |
| | PROPOSED FIRE HYDRANT. |
| | |
| | 9. PLEASE VERIFY THAT THE SUBMITTED CERTIFIED COST |
| | ESTIMATE INCLUDES THE REQUIRED IMPROVEMENTS WITHIN THE |
| | FLAGLER RIGHT-OF-WAY. |
| | |
| | 10. ON THE CERTIFIED COST ESTIMATE: THE LANDSCAPING, |
| | REMOVAL OF ELECTRICAL EQUIPMENT, SITE FURNISHINGS, |
| | CONCRETE WALL, ALUMINUM FENCE, AND EXTERIOR LIGHTING |
| | WILL BE COVERED UNDER A BUILDING PERMIT FROM THE CITY |
| | OF WEST PALM BEACH. PLEASE REVISE THE FORM TO HAVE A |
| | ?Y? IN THE GRAY COLUMN. AS A RESULT, THE DEVELOPMENT |
| | REVIEW FEE WILL DECREASE TO APPROXIMATELY $19,700. |
| | |
| | |
| | KELLY CRANFORD, P.E. |
| | LAND DEVELOPMENT ENGINEER |
| | [email protected] |
| | 561-494-1098 (OFFICE) |
| | |
| 2015-04-29 10:28:33 | FLORIDA POWER AND LIGHT ?MANATEE EDUCATION CENTER PLAN |
| | REVIEW COMMENTS: |
| | |
| | #1 TAP AND PIPING ON N. FLAGLER SHOULD BE SHOWN WITH |
| | MINIMAL FITTINGS AND ALIGNMENT. THE CITY PREFERS YOU |
| | USING THE 45 DEGREE BENDS ON-SITE. |
| | THIS WOULD ALSO AVOID CONFLICT WITH EXISTING TREE IN |
| | R-O-W. SHOW CLEARANCE BETWEEN WATER AND SEWER WHERE |
| | DOMESTIC WATER AND FIRELINE CROSS SANITARY SEWER. |
| | |
| | #2 SHOW VERTICAL CLEARANCES BETWEEN ON-SITE WATER AND |
| | FIRE WHERE THEY CROSS SANITARY FORCEMAIN. |
| | |
| | #3 FIRE DEPARTMENT CONNECTION (FDC) LOCATION IS NOT |
| | SHOWN. |
| | |
| | #4 CUT BACK AT MAIN THE EXISTING WATER SERVICE(S) THAT |
| | WILL NOT BE IN USE. RESTORE PAVEMENT AS PER CITY OF WPB |
| | STANDARDS. SHOW PAVEMENT RESTORATION AREA SHADED AT |
| | THOSE LOCATIONS. |
| | |
| | #5 METERS AND FIRELINE GATE VALVE TO BE INSTALLED IN |
| | CITY OF WPB RIGHT-OF-WAY JUST OUTSIDE OF YOUR PROPERTY |
| | LINE. THIS WOULD AVOID THE EXPENSE OF SUPPLYING THE |
| | CITY WITH AN EASEMENT AND WILL ALSO ALLOW METERS TO BE |
| | EASILY ACCESSIBLE. BACKFLOWS ARE PRIVATE AND SHOULD BE |
| | LOCATED JUST INSIDE YOUR PROPERTY. |
| | |
| | #6 SHEETS C-6.07 SHOWS GENERAL NOTES GN-7 AND GN-8 TOO |
| | LIGHT AND HARD TO READ. |
| | |
| | #7 EXISTING CONCRETE APRONS NOT NEEDED SHALL BE REMOVED |
| | AND RESTORED WITH SIDEWALK. |
| | |
| | #8 C4.01 WATER AND SEWER PLAN - SHOW EXISTING SANITARY |
| | SEWER MANHOLE AND EXISTING STORM DRAINAGE MANHOLE AT |
| | STREET 59TH ST AND N. FLAGLER. |
| | |
| | #9 NO STRIPING PLAN FOR 59TH ST AND N. FLAGLER. |
| | STRIPING MUST BE RESTORED TO EQUAL OR BETTER. |
| | THERMOPLASTIC SHOULD BE USED. WHITE THERMO STOP BAR |
| | SHALL BE INSTALLED AT 59TH ST AND N. FLAGLER - |
| | SOUTHBOUND. |
| | |
| | #10 PROPOSED DRIVEWAYS SHOULD BE PER CITY OF WPB |
| | STANDARDS - CONCRETE TYPE APRONS. |
| | |
| | #11 C-4.01 ..NOTE: UTILITY PLANS PENDING CITY OF |
| | RIVIERA BEACH UTILITY APPROVAL.. NOT NEEDED. |
| | |
| | #12 THERE IS NO IRRIGATION METER SHOWN. IT IS SUGGESTED |
| | AS YOU HAVE LANDSCAPING REQUIREMENTS. |
| | |
| | FORMAL STORMWATER COMMENTS WILL BE ADDED BY KELLY |
| | CRANFORD, P.E. AS SOON AS THEY ARE GENERATED. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |
| | |
| | |
| | |
| | |