Plan Review Details - Project E14070002
Plan Review Stops For Project E14070002
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date 07-07-2014 Time   Rev Time 6.00
Received By cranford Date 06-18-2014 Time 15:30 Sent To  
Notes
2014-07-07 15:31:32DISCUSSED ON PHONE WITH ENGINEER, THEN EMAILED
 COMMENTS.
  
 THE FOLLOWING INFORMATION IS NEEDED TO COMPLETE THE
 ENGINEERING DEPARTMENT REVIEW OF THE APPLICATION FOR A
 DEVELOPMENT PERMIT AT 4201 GEORGIA AVENUE.
  
 PLEASE DEMONSTRATE THAT THE FOLLOWING CONDITIONS OF
 INFORMAL SITE PLAN APPROVAL HAVE BEEN MET:
 1.C. APPLY FOR AND RECORD THE UNITY OF TITLE
 1.D. DEMONSTRATE THE WORK PROPOSED WITHIN THE EXISTING
 EASEMENTS IS ACCEPTABLE TO THE EASEMENT HOLDER(S)
 3. OBTAIN A RIGHT-OF-WAY PERMIT FOR THE WORK PROPOSED
 WITHIN THE CITY?S RIGHT-OF-WAYS
  
 SUBMIT ONE (1) COMPLETE SET OF FINAL SITE PLAN APPROVAL
 DRAWINGS. THE FINAL SET WILL BE STAMPED AS APPROVED BY
 THE CITY OF WEST PALM BEACH PLANNING DEPARTMENT.
  
 PLEASE SUBMIT A SIGNED AND SEALED BOUNDARY SURVEY. THE
 SURVEY SHOULD SHOW ALL EXISTING EASEMENTS.
  
 PLEASE PROVIDE A COST ESTIMATE WHICH INCLUDES ONLY THE
 CONSTRUCTION PROPOSED WITHIN THE CITY?S EASEMENTS OR
 RIGHT-OF-WAYS.
  
 PLEASE PROVIDE A COPY OF THE FINAL LANDSCAPE PLAN.
 - IN ADDITION TO BEING INSTALLED ALONG THE EXFILTRATION
 TRENCH AND STORMWATER PIPING (NOTE 1 ON SHEET C-1),
 ROOT BARRIERS SHOULD ALSO BE INCLUDED FOR THOSE
 PLANTINGS WITHIN FIVE FEET OF ALL MUNICIPAL OWNED
 UTILITIES. PLEASE INCLUDE PLAN VIEW AND PROFILE FOR THE
 ROOT BARRIERS LOCATIONS. THE ROOT BARRIERS MUST BE
 LOCATED AT LEAST FIVE FEET FROM ALL UTILITIES, A
 MINIMUM OF 42 INCHES DEEP, AND AT LEAST 15 FEET LONG
 CENTERED ON A TREE.
 - THE LANDSCAPE PLAN SHOULD ALSO INCLUDE DETAILS OF THE
 PROPOSED PRIVACY WALL.
  
 CONSTRUCTION PLANS
 PLEASE INCLUDE A DETAIL FOR THE EXFILTRATION TRENCH
 CONTROL STRUCTURE.
  
 ALTHOUGH THE CITY'S PROJECT AT THIS INTERSECTION IS
 PLANNED TO BEGIN CONSTRUCTION WITHIN THE NEXT YEAR, THE
 SCHEDULE MAY NOT COINCIDE WITH THE DEVELOPMENT OF THIS
 PARCEL. WHAT CONTINGENCY PLANS HAVE BEEN MADE IN THE
 EVENT CONSTRUCTION OF THIS PARCEL PROCEEDS BEFORE THE
 CITY?S PLANNED UTILITY CONSTRUCTION AND INTERSECTION
 IMPROVEMENTS?
  
 PLEASE SUBMIT CONSTRUCTION PLANS FOR THE IMPROVEMENTS
 PROPOSED WITHIN THE RIGHT-OF-WAY TO SUPPORT DEVELOPMENT
 OF THIS PARCEL.
  
 THE DRIVEWAY ON GEORGIA AVENUE IS CENTERED ON TWO
 EXISTING POWER POLES. HAVE THE OWNERS OF THE POLES BEEN
 CONTACTED TO DETERMINE IF THE POLES CAN BE RELOCATED?
  
 THERE IS ALSO AN EXISTING ABOVE GROUND VALVE LOCATED
 JUST SOUTH OF THE DRIVEWAY. WILL THIS VALVE BE REMOVED
 OR RELOCATED? IF THE LINE IS GOING TO BE ABANDONED,
 PLEASE INDICATE THAT THE LINE WILL BE REMOVED.
  
 PLEASE REVISE THE SIDEWALK-DRIVEWAY CROSSINGS TO
 INCLUDE DETECTABLE WARNINGS THAT MEET FLORIDA
 ACCESSIBILITY CODE AND ADA GUIDELINES.
  
 THE PLANS SHOW AN EXISTING OVERHEAD UTILITY LINE
 CROSSING OVER THE PROPOSED NORTHERN BUILDING
 (PHARMACY). IS THE OVERHEAD LINE NOT IN AN EXISTING
 EASEMENT? PLEASE VERIFY THAT THE VERTICAL CLEARANCE IS
 SUFFICIENT FOR CONSTRUCTION OF THE BUILDING.
  
 PLEASE SHOW THE LOCATIONS OF THE BACKFLOW PREVENTERS
 FOR THE PROPOSED WATER SERVICES. IF ANY OF THE
 BUILDINGS ARE PROPOSED TO BE SPRINKLED, PLEASE SHOW THE
 LOCATION OF THE FIRE LINES.
  
 ARE THE SANITARY SERVICE LINES PROPOSED TO TIE INTO
 EXISTING LATERALS OR ARE NEW CONNECTIONS PROPOSED?
 PLEASE NOTE THAT THE PIPE SIZE BETWEEN THE MAIN LINE
 AND THE WYE SHOULD BE A MINIMUM SIZE OF 6-INCHES IN
 DIAMETER.
  
 ADDITIONAL COMMENTS
 PRIOR TO SCHEDULING PRECONSTRUCTION MEETING, THE
 FOLLOWING DOCUMENTS MUST BE SUBMITTED TO ENGINEERING:
 - NPDES PERMIT
 - DEWATERING PERMIT (IF DEWATERING IS PROPOSED)
 - A COPY THE FDEP SELF-CERTIFICATION FOR A STORMWATER
 MANAGEMENT SYSTEM IN UPLANDS SERVING LESS THAN 10 ACRES
 OF TOTAL PROJECT AREA AND LESS THAN 2 ACRES OF
 IMPERVIOUS SURFACE OR SFWMD PERMIT.
  

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***