Plan Review Details - Project E14060020
Plan Review Stops For Project E14060020
Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 06-27-2014 Cont ID  
Sent By   Date 06-27-2014 Time   Rev Time 6.00
Received By   Date 06-17-2014 Time   Sent To  
Notes
2014-06-27 15:10:38LAND DEVELOPMENT REVIEW COMMENTS
 BELMART PLAZA PUBLIX
 PROJECT E14060020
  
 PLEASE RESPOND TO THE FOLLOWING COMMENTS IN WRITTING.
  
 SITE PLAN
 PLEASE SUBMIT ONE (1) COMPLETE SET OF APPROVED SITE
 PLAN DRAWINGS. THE APPROVED DRAWINGS WILL HAVE BEEN
 STAMPED BY THE CITY OF WEST PALM BEACH PLANNING
 DEPARTMENT.
  
 SUPPORTING DOCUMENTATION
 PLEASE SUBMIT COPIES OF REGULATORY PERMIT APPROVALS
 (I.E. FDEP SELF-CERTIFICATION FOR A STORMWATER
 MANAGEMENT SYSTEM IN UPLANDS SERVING LESS THAN 10 ACRES
 OF TOTAL PROJECT AREA AND LESS THAN 2 ACRES OF
 IMPERVIOUS SURFACE OR SFWMD PERMIT, PALM BEACH COUNTY
 PERMIT FOR WORK WITHIN BELVEDERE ROAD RIGHT-OF-WAY).
 THE SUBMITTED BOUNDARY SURVEY WAS NOT SIGNED OR SEALED.
 PLEASE SUBMIT A SIGNED AND SEALED COPY OF THE BOUNDARY
 SURVEY.
 PLEASE PROVIDE A COPY OF THE PROPOSED STORMWATER
 POLLUTION PREVENTION PLAN.
 PLEASE REVISE THE COST ESTIMATE TO INCLUDE ONLY THE
 CONSTRUCTION PROPOSED WITHIN THE CITY?S EASEMENTS OR
 RIGHT-OF-WAYS. (SEE ATTACHED)
 PLEASE PROVIDE COPIES OF THE FIRE FLOW AND STORMWATER
 CALCULATIONS.
  
 CONSTRUCTION PLANS
 SHEET C-02: NOTES 1 AND 7 REFER TO A BOUNDARY SURVEY
 WITH A REVISION DATE OF 2012. THE SUBMITTED SURVEY
 SHOWS A REVISION DATE OF APRIL 21, 2014. PLEASE VERIFY
 THAT THE NOTES REFER TO THE LATEST SURVEY REVISION
 DATE.
 SHEET C-03: WHERE IS THE CONSTRUCTION FENCE PROPOSED?
 THE NOTE BELOW THE CONSTRUCTION FENCE DETAILS
 REFERENCES STUDENTS AND SCHOOL PERSONNEL AND DOES NOT
 APPEAR TO APPLY TO THIS PROJECT.
 SHEET C-04: PLEASE INCLUDE A LEGEND DEFINING THE
 VARIOUS LINE TYPES.
 AT THE END OF THE SEWER AND WATER SERVICE SEGMENTS
 SHOWN AS TO BE REMOVED, PLEASE INCLUDE A DESCRIPTION
 FOR PLUGGING/BLOCKING SANITARY SERVICE MAIN THAT WILL
 REMAIN IN PLACE. FOR CLARIFICATION ON THE AS-BUILT
 DRAWINGS, CONSIDER SHOWING THE REMOVAL NOTES ON SHEET
 C-09.
 PLEASE SHOW THE LOCATION OF THE EXISTING WATER SERVICE
 LINES WITHIN 50 FEET OF THE PROPOSED PUBLIX. PRIMARY
 CONCERN IS FOR THOSE LINES WEST OF THE PROPOSED PUBLIX
 IN THE VICINITY OF THE PROPOSED SANITARY LATERAL AND
 FORCE MAIN EXTENSIONS.
 SHEET C-06: PLEASE REVISE THE CALL-OUT FOR CATCH BASIN
 C-4 TO INCLUDE THE WEIR FOR THE EXFILTRATION TRENCH.
 PLEASE REVISE EITHER THE CALL-OUT FOR THE EXFILTRATION
 TRENCH ON THIS SHEET OR THE DESCRIPTION ON THE DETAIL
 (SHEET C-07) SO THAT THEY MATCH.
 HOW IS THE PROPOSED 15-INCH CMP GOING TO CONNECT TO THE
 EXISTING CMP WEST OF CATCH BASIN C-1? (PLEASE PROVIDE A
 DETAIL.)
 SHEET C-07: THE ELEVATIONS SHOWN ON THE EXFILTRATION
 TRENCH DETAIL DO NOT APPEAR TO MATCH THE FINISHED GRADE
 OR PIPE INVERT ELEVATIONS SHOWN ON THE PLAN VIEW. THE
 TRENCH WIDTH DOES NOT MATCH CALL-OUT ON PLAN SHEET
 C-06. PLEASE REVISE THE DETAIL SO IT MATCHES THE
 INFORMATION SHOWN ON THE OTHER PLAN SHEETS. PLEASE ALSO
 VERIFY THAT SHOWN SEASONAL HIGH WATER ELEVATION IS
 APPROPRIATE FOR THIS SITE.
 SHEET C-09: IS A NEW WATER SERVICE CONNECTION PROPOSED
 OR IS SERVICE PROPOSED TO TIE INTO THE EXISTING
 LATERAL, WHICH OUR RECORDS INDICATE IS SERVED BY A
 VALVE THAT IS OVER 60 YEARS OLD? IF A NEW CONNECTION IS
 NOT PROPOSED, PLEASE ADD A NOTE TO THE PLANS INDICATING
 THAT A NEW WATER SERVICE CONNECTION WILL BE REQUIRED IF
 CONNECTING TO THE EXISTING LINE IS NOT FEASIBLE.
 PLEASE PROVIDE A DETAIL OF THE PROPOSED UTILITY
 EASEMENT. THE DDCV WILL BE PRIVATELY OWNED AND SHOULD
 BE EXCLUDED FROM THE EASEMENT AREA.
 PLEASE PROVIDE CROSSING DETAILS FOR ALL UNDERGROUND
 UTILITY CROSSINGS.
 WHAT IS THE PURPOSE OF THE PROPOSED STORMWATER MANHOLE
 SHOWN SOUTHWEST OF THE NEW LOADING DOCK?
 SHEET LP-1: PLEASE VERIFY THAT THE DRIP LINES AND ROOT
 ZONES FOR ANY NEW TREES AND SHRUBS WILL BE LOCATED
 OUTSIDE OF THE PROPOSED UTILITY EASEMENT. THE CITY WILL
 NOT BE RESPONSIBLE FOR REPLACEMENT OF ANY LANDSCAPING
 LOCATED WITHIN THE UTILITY EASEMENT.
 SHEET LI-1: PLEASE REMOVE THE IRRIGATION FEATURES SHOWN
 WITHIN THE PROPOSED UTILITY EASEMENT.
  
 ADDITIONAL COMMENTS
 NPDES AND DEWATERING PERMIT (IF DEWATERING IS PROPOSED)
 ARE TO BE SUBMITTED PRIOR TO SCHEDULING PRECONSTRUCTION
 MEETING.
 AS-BUILT DRAWINGS WILL NEED TO INCLUDE LOCATIONS OF
 FP&L CONDUIT, FLORIDA PUBLIC UTILITIES GAS SERVICE
 LINE, AT&T CONDUIT.
 A DRAFT UTILITY EASEMENT NOT SUBMITTED. PLEASE SUBMIT
 PRIOR TO FINAL APPROVAL.
  

Review Stop ENG-D ENGINEERING DEFICIENCY REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-E ENGINEERING ENVR. MIT. REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG-T ENGINEERING TRAFFIC STUDY REV
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***