| 2014-04-15 08:52:41 | REVIEW - LOFTIN PLACE 04/14/2014 |
| | #1 NOTE ON PLANS THAT MASTER METER WILL BE INSTALLED |
| | ABOVE GROUND. |
| | #2 SEPARATE DOMESTIC TAP FROM FIRE TAPP |
| | #3 TAPPING VALVE AND SLEEVE CAN BE THE VALVES FOR FIRE |
| | AND DOMESTIC. NO NEED FOR ADDITIONAL VALVES. |
| | #4 CALL OUT MATERIAL OF PIPE AT THE UTILITY CROSSING |
| | TABLE FOR WATER SEWER AND STORM. |
| | #5 FDC LOCATION SHALL BE JUST INSIDE THE PROPERTY AND |
| | NOT ON CITY OF WPB R.O.W. |
| | #6 WATER LINES FOR FUTURE SERVICE MUST SHOW VERTICAL |
| | CLEARANCES AND PIPE MATERIAL CALL OUT. |
| | #7 NOTE ON PLANS: STORM STRUCTURE THAT IS REMAINING ON |
| | EUCAPYPTUS STREET CANNOT REMAIN IF BRICK. MAKE NOTE |
| | PROVISIONS TO REPLACE IN THE EVENT THE STRUCTURE IS |
| | BRICK. |
| | #8 ALL PIPING FOR 3 INCH METER TO BE 4 INCH DIAMETER |
| | DIP. |
| | #9 NOTE ON PLANS: CITY ONLY GUARANTEES ADEQUATE WATER |
| | PRESSURES TO 2ND STORY; BEYOND MUST BE THRU PRIVATE |
| | PUMPING SYSTEM. |
| | #10 WATER SERVICE STUB FROM NORTH DIXIE UNTO PARCEL C |
| | MUST BE CUT AND CAPPED AT MAIN. I WOULD SUGGEST |
| | REDUCING AND UTILIZING FOR A IRRIGATION SERVICE. |
| | #11 OLD WATER SERVICES MUST BE CUT BACK TO MAIN. NOTE |
| | TO BE CUT, CAPPED AND RESTRAINED AT MAIN. |
| | #12 SHOW EXISTING FIRE HYDRANT AT 6TH STREET AND OLIVE |
| | AVENUE. |
| | #13 NOTE ON PLANS THAT ANY DISTURBANCE BROUGHT UPON |
| | EXISTING INFRASTRUCTURE SUCH AS WATER, SEWER AND STORM |
| | DUE TO ROW WORK IS THE RESPONSIBILITY OF THE CONTRACTOR |
| | TO REPLACE TO EQUAL OR BETTER. |
| | #14 SHOW ALL SIDEWALK PATH EASEMENTS. THIS SHOULD |
| | INCLUDE ADA ACCESS AROUND THE PERIMETER OF THE SITE |
| | INCLUDING INTERACTION UNTO EXISTING SIDEWALKS AND |
| | ADJACENT STREETSCAPES. SHEET C-09 WOULD BE MY |
| | SUGGESTION. CALL OUT MATERIAL OF SURFACES; THAT BEING |
| | CONCRETE, PAVERS, ASPHALT ETC. ALL APRONS MUST BE 6 |
| | INCH THICK 3000PSI CONCRETE MINIMUM. |
| | #15 STREET LIGHTS NOT SHOWN, NOR DO I SEE AN IRRIGATION |
| | PLAN. THIS ALL WILL FALL ON THE DEVELOPER TO OBTAIN A |
| | MAINTENANCE AGREEMENT WITH THE CITY. CONTACT VINCENT |
| | NOEL AT CITY OF WPB ENGINEERING (561) 494-1096. |
| | #16 CALL OUT STRIPING TO BE (THERMOPLASTIC) |
| | #17 NOTE: EXIST CONCRETE SANITARY MANHOLES IN THE ROW |
| | THAT WILL BE CONNECTED TO WILL HAVE TO BE REHABILITATED |
| | PER CITY OF WPB STANDARDS OR REPLACED IF FOUND TO BE OF |
| | BRICK MATERIAL. |
| | |
| | |