| 2013-11-12 21:05:43 | PASSED WITH PROVISOS: |
| | |
| | #1 DIRECT TAP FOR DOMESTIC AND FIRE WILL BE DONE |
| | INDEPENDENT OFF EACH OTHER TIED BACK TO THE 12" DIP WM. |
| | PROPER CLEARANCE AND PIPE RESTRAINTS MUST BE USED |
| | DURING THIS INSTALLATION. |
| | |
| | #2 IRRIGATION SERVICES WILL REQUIRE AN RPZ JUST INSIDE |
| | THE PROPERTY. |
| | |
| | #3 IRRIGATION CONDUITS WILL BE REQUIRED FOR LANDSCAPE |
| | ISLANDS IN THE ROW OF HIBISCUS. |
| | |
| | #4 EXISTING STORM WATER PIPING IN CITY ROW OR EASEMENTS |
| | ABANDONED IN PLACE MUST BE REMOVED WHEN POSSIBLE. |
| | FLOWABLE FILL WOULD BE CONSIDERED AN ALTERNATE OPTION |
| | AS APPROVED. |
| | |
| | #5 CONTRACTOR MUST IMPLEMENT NPDES AND SHALL |
| | IMPLEMENTPOLLUTION PREVENTION FOR ALL WORK IN ROW. |
| | |
| | #6 AS-BUILTS AND E.O.R. CERTIFICATION WILL BE REQUIRED |
| | FOR THIS PROJECT. |
| | |
| | #7 ROW PERMIT IS REQUIRED FOR WORK PERFORMED IN ROW. |
| | |
| | #8 48 HOUR NOTICE MUST BE PROVIDED THRU EOR TO CITY'S |
| | ASSIGNED CONSTRUCTION COORDINATOR. |
| | |
| | #9 ANY ROW WORK WILL REQUIRE A CERTIFIED MAINTENANCE OF |
| | TRAFFIC PLAN APPROVED BY CITY'S TRAFFIC ENGINEER. |
| | |
| | #10 LARGE DOMESTIC METER WILL BE INSTALLED ABOVE |
| | GROUND, CONTRACTOR MUST FOLLOW THE RECOMMENDED |
| | INSTALLATION PROCEDURE FROM THE MANUFACTURER |
| | WHICH OUTLINES METER POSITION AND COMPONENT SPACING |
| | WHICH ALLOWS THE METER TO READ WITH ACCURACY. METER |
| | LOCATION WILL REQUIRE A UTILITY EASEMENT. |
| | SUBMISSION OF A LEGAL AND SKETCH SURVEY DESCRIPTION |
| | WILL BE SUBMITTED BY THE OWNER FOR CITY TO REVIEW, |
| | ACCEPT AND RECORD IN PUBLIC RECORDS. |
| | |
| | #11 EXTENTS OF PAVEMENT REPLACEMENT WILL BE DETERMINED |
| | AREAS DISTURBED DURING EXCAVATION AND AS SET FORTH ON |
| | ROW PERMIT SPECIFICATIONS. |
| | FURTHER ENQUIRE SHALL BE MADE THRU THE CITY TRAFFIC |
| | ENGINEER'S OFFICE. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |