| 2013-07-22 08:17:33 | COMMENTS FROM STORM WATER SECTION: |
| | |
| | SHEET C002: |
| | 1. W&S SPECS NOTE 13 - SHOULD NOTE REFER TO WEST PALM |
| | BEACH WATER UTILITIES DEPARTMENT INSTEAD OF PALM BEACH |
| | COUNTY UTILITIES? WHOSE WATER MAIN WILL BE TAPPED? |
| | 2. WATER DISTRIBUTION MATERIAL SPECS PER PUD NOTE 07 - |
| | WEST PALM BEACH WATER UTILITIES DEPARTMENT INSTEAD OF |
| | WPB UTILITIES COMMISSION? MAKE REFERENCE TO CWPB |
| | APPROVED MATERIALS LIST? |
| | 3. CWPB SEWAGE COLLECTION/TRANSMISSION NOTES NOTE 06 - |
| | WRONG PHONE NUMBER LISTED. |
| | |
| | SHEET C100 |
| | 4. ALTHOUGH THERE IS A GENERAL NOTE ON SHEET C001 |
| | INDICATING ELEVATIONS ARE SHOWN IN NGVD1929, NOTE 3 ON |
| | SHEET C100 PROVIDES A CONVERSION BETWEEN NAVD AND NGVD. |
| | THE NOTE SHOULD INDICATE NGVD ELEVATIONS ARE SHOWN ON |
| | THE SHEET. |
| | |
| | SHEET C200 |
| | 5. FOUR (4) KEEP RIGHT SIGNS (R4-7C) BE INSTALLED IN |
| | THE MEDIANS OF LAMBERTON DRIVE. |
| | 6. CROSS WALK STRIPING AND CROSS WALK SIGNS NEEDED AT |
| | PEDESTRIAN CROSSING ON LAMBERTON DRIVE EAST OF |
| | APARTMENT ENTRANCE. |
| | 7. CROSS WALK STRIPING NEEDED ACROSS LAMBERTON DRIVE AT |
| | INTERSECTION WITH EXECUTIVE CENTER DRIVE. |
| | |
| | SHEET C650 |
| | 8. WHAT IS THE "WASTEWATER BUREAU" REFERENCED IN THE |
| | FRAME CAST IN TOP SLAB DETAIL? |
| | |
| | SHEET L1.11 |
| | 9. OAK TREE PROPOSED NEAR PROPOSED STORM PIPE SOUTHWEST |
| | OF TRASH COMPACTOR BUILDING. ROOT BARRIER PROPOSED? |
| | |
| | 10. YELLOW POINCIANA TREE PROPOSED NEAR PROPOSED STORM |
| | PIPE WEST OF CLUBHOUSE. ROOT BARRIER PROPOSED? |
| | |
| | DRAINAGE CALCS: |
| | 11. CN FOR A/D SOILS SHOULD USE THE CN FOR TYPE A SOILS |
| | IF THE WATER TABLE IS DRAINED. IF THE WATER TABLE IS |
| | ELEVATED WHERE IT WILL AFFECT INFILTRATION, THE A/D |
| | SOILS REACT MORE LIKE TYPE D SOILS WITH MORE RUNOFF |
| | POTENTIAL AND THE CN VALUE FOR TYPE D SOILS SHOULD BE |
| | USED. |
| | |
| | TRACY L. WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |
| | CITY OF WEST PALM BEACH |
| | ENGINEERING AND PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS ST., 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 561-494-1120 |
| | FAX: 561-494-1116 |
| | CELL 561-351-0510 |
| | [email protected] |
| | |
| | ************************************** |
| | |
| | JEFFERSON |
| | |
| | SHEET C001 STORM SEWER NOTES MAKES REFERENCE TO CITY |
| | SECTION 09/03/05. COULD YOU PROVIDE SUCH SPECIFICATION. |
| | YOU MAY PDF VIA E-MAIL TO [email protected] |
| | |
| | SHEET C002 CITY OF WPB WATER DISTRIBUTION NOTES- THESES |
| | NOTES CONFLICT WITH CITY OF WPB STANDARD NOTES FOR FIRE |
| | HYDRANT LOCATION SPECIFICATION AND COLOR. PLEASE |
| | REMOVE. IT IS SUGGESTED THAT EVEN THOUGH FIRE HYDRANTS |
| | ARE PRIVATE THEY ARE TO MATCH CITY OF WPB STANDARDS FOR |
| | SAFETY OF OPERATIONS. |
| | |
| | SHEET C403 METER TAP LOCATION REQUIRES ISOLATION |
| | VALVES. 4" RWGV MUST BE PLACES WHERE 4" TEE PROVIDE |
| | WATER TO METER AREA. FOR FIRE LINE IT IS REQUIRED THAT |
| | YOU PROVIDE AN 8" RWGV TO BE ABLE TO SHUTDOWN THE |
| | FIRELINE.3" METER PIPING SHALL BE AS PER CITY STANDARD |
| | WHICH IS 4" DIAMETER PIPING UP TO AND FROM THE METER, |
| | REDUCER S ARE PLACED TO ACCOMMODATE 3" METER. REFER TO |
| | CITY OF WPB STANDARDS WS-6 3 & LARGER DOMESTIC METER |
| | DETAIL AND W-6.1 3 & LARGER METER LEGEND . METER PIPING |
| | AND FIRELINE PIPING UP TO BACK OF BACKFLOW MUST BE OF |
| | DUCTILE IRON PIPE MATERIAL, YOU MAY USE PVC BEYOND |
| | BACKFLOW. |
| | |
| | SHEET C402 AND C403 SHOW SEWER SERVICES IN EXCESS OF 75 |
| | LF. A CLEANOUT SHALL BE PLACED EVERY 75 LINEAR FEET. |
| | |
| | SHEET C400 SERIES ARE MISSING AT LEAST TWO WATER MAIN |
| | CONFLICT CALL OUTS. |
| | |
| | SHEET C640 WATER JUMPER DETAIL PLEASE REFER AND USE THE |
| | CITY OF WPB STANDARD DETAIL P-6 PIGGING PROCEDURE. THIS |
| | DETAIL SHOWS ACCEPTABLE PRACTICE THAT WILL KEEP YOU IN |
| | COMPLIANCE WITH PALM BEACH COUNTY HEALTH DEPARTMENT |
| | RULES. |
| | |
| | SHEET C640 TABLE FOR CONFLICTS SHOWS 4" DIAMETER PIPING |
| | WHERE 3" IS SHOWN ON PLANS. PLEASE REVIEW CROSSING |
| | LOCATIONS #6, #8, #13, #15, #23, #31, AND #32. WHERE |
| | SEWER SERVICES ARE SHOWN WITH LESS THAN 30" OF COVER IT |
| | IS HIGHLY SUGGESTED THAT YOU USE CLASS 50 DIP MATERIAL |
| | PIPING VS PVC. CONFLICT #16 SHOULD INCLUDE 3" WM. |
| | |
| | SHEET C650 MANHOLE TOPS SHOWN CONFLICT WITH CITY OF WPB |
| | STANDARDS SHOWN ON SHEET C651 GS-1 MANHOLE COVER & |
| | FRAME AND GS-2 MANHOLE, TYPICAL . REVIEW DETAILS ON |
| | C650 AS SOME DIMENSIONS ARE SHOWN INCORRECT AS COMPARED |
| | TO SPECIFICATIONS IS U.S. FOUNDRY CATALOG FOR THE |
| | SPECIFIED MANHOLE TOP MODELS. NO BRICKS SHALL BE USED |
| | FOR PLACEMENT OF MANHOLE RING AND COVER. RISER RINGS |
| | ONLY. |
| | |
| | ENTRANCE DRIVEWAY MUST BE AS PER CITY OF WPB STANDARD |
| | CONCRETE APRON GC-6 DRIVEWAY APRONS. |
| | |
| | FEEL FREE TO REVISE THE SUBJECT SHEETS. ONCE REVISED WE |
| | MAY INSERT THEM INTO THE SETS FOR SIGN OFF AND PROCEED |
| | WITH PALM BEACH COUNTY HEALTH DEPARTMENT PERMIT FOR |
| | WATER MAINS AND DEP PERMITTING FOR SEWER. |
| | |
| | |
| | |
| | |
| | |