| 2013-04-25 15:19:46 | PLAN COMMENTS: |
| | |
| | STATUS IS FAILED. |
| | |
| | #1 PLANS DO NOT SHOW STRAIGHT PIPE DISTANCE BEFORE AND |
| | AFTER METER. |
| | |
| | #2 2" FM CONNECTION IS UNACCEPTABLE WITH SO MANY |
| | FITTINGS. DIRECT TAPP WOULD BE ACCEPTABLE. FORD 202BS |
| | DOUBLE BAND BRASS SADDLE. |
| | |
| | #3 PROVIDE APPROVED MATERIAL LIST WITH METER BOX |
| | COATING INTERNAL AND EXTERNAL FOR SEWER COATINGS (USE |
| | MANHOLE COATING SECTION TO SELECT.) |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | #4 PROVIDE DIMENSIONS AND DISTANCES FROM EXISTING |
| | STRUCTURE TO PROPOSED STRUCTURE. |
| | |
| | #5 METER INSTALL RECOMMENDATIONS MUST MEET |
| | SPECIFICATION. PROVIDE CROSS SECTION OF 2" METER |
| | INSTALL SHOWING HORIZONTAL PLACEMENT. |
| | IT MUST BE INSTALLED IN A MANNER WHERE OPTIMUM METER |
| | ACCURAZY AND PERFORMANCE IS ACHIEVED. IT IS RECOMMENDED |
| | TO CONTACT METER SUPPLIER TO ASSIST IN THIS |
| | INSTALLATION TO ACHIEVE OPTIMUM PERFORMANCE. CONTACT |
| | CITY METER SHOP FOR METER TECHNICAL SUPPORT CONTACT |
| | INFORMATION (561) -822-1200. |
| | |