Plan Review Details - Project E12070037
Plan Review Stops For Project E12070037
Review Stop ENG-USR ENGINEERING-UTY. SER. REVIEW
Rev No 1 Status F Date 02-01-2013 Cont ID  
Sent By mgonzale Date 02-01-2013 Time   Rev Time 24.00
Received By mgonzale Date 12-14-2012 Time   Sent To  
Notes
2013-02-01 10:56:11RESPOND TO COMMENTS IN WRIRTTING:
  
 PLANS REFLECT A NEW TAP FOR DOMETIC WATER. (TAP WILL
 NOT BE APPROVED AT THE SPECIFIED LOCATION DUE TO THE WM
 THAT IT IS CONNECTED TO WILL BE PLACED OUT OF SERVICE
 IN NEAR FUTURE.) REVISE SHOWING TAP OFF 6" WATERMAIN
 LEG FEEDING THE BUILDING NOW (BEFORE FIRELINE CONTROL
 VALVE). (A SKETCH HAS BEEN SENT VIA EMAIL 02/01/2013
 SHOWING AVAILABILITY OF SERVICE OPTIONS)
  
 ON THAT SAME NOTE: FOR PROPOSED FIRELINE PLEASE LOOK
 INTO THE OPTION OF CONNECTING TO EXISTING 6" WATERMAIN
 LEG. THIS MAIN WOULD REQUIRED A 6" RW GATE VALVE TO BE
 ABLE TO SHUT OFF AND TURN 90 DEGREES TO GRASSED AREA ON
 THE WEST SIDE OF BUILDING WHERE DCDA CAN BE PLACED. YOU
 DCDA IS PRIVATE SO THE CITY WILL NOT REQUIRE EASEMENT.
 FOR METER SERVICE THE CITY WILL REQUIRED AN 5' EASEMENT
 COVERING THE SERVICE UNDER SIDEWALK ALL THE WAY TO THE
 METER (IT SHOULD COVER THE METER AREA). THE EASMENT
 DOCUMENT CAN BE EMAIL TO YOU IF REQUEST IS MADE TO
 VINCENT NOEL (561) 494-1096.
 A LEGAL AND SKETCH WILL HAVE TO BE PRESENTED AT OWNERS
 EXPENSE.
  
 CONTRACTOR MUST ALSO PROVIDE FDC LOCATION ON PLANS AND
 IT MUST BE WITHIN 150 LINEAR FEET AWAY FROM NEAREST
 CITY FIRE HYDRANT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved