| 2011-11-21 08:19:18 | TEMPORARY CONSTRUCTION VILLAGE COMMENTS: ESD PERMIT # |
| | E11100001 |
| | |
| | #1 PLAN SHOW USING PVC MATERIAL ON THE CITY SIDE, CITY |
| | ONLY ACCEPTS DIP (DUCTILE IRON PIPE), SHEET 700-CO-017 |
| | |
| | #2 PLAN LACKS THE PROPERTY LINE AROUND THE ENTIRE SITE. |
| | THIS IS IMPORTANT TO SHOW ON SHEETS WHERE BMP'S AND |
| | NPDES ELEMENTS ARE USED TO CONTROL CONSTRUCTION |
| | ACTIVITY. |
| | |
| | #3 PLEASE PROVIDE USAGE INFORMATION FOR WATER AND |
| | SEWER. GPM, ETC. SPECIFY USING NEPTUNE PROTECTUS IIIS |
| | FIRE SERVICE METER. SHEET 700-CO-017 |
| | METER VAULT AND BACKFLOW SHOULD BE ORIENTED - RUNNING |
| | NORTH AND SOUTH SAME AS BACKFLOW. |
| | NOTE: (6" FIRE PER AWWA 900 - 2,000 (HEAD LOSS 12 PSI) |
| | (CAN FEED FIRE HYDRANTS ON-SITE AND POTABLE WATER) |
| | AWWA SAYS 1600 GPM (6PSI LOSS NEPTUNE) = 6? NEPTUNE |
| | PROTECTUS IIIS FIRE SERVICE METER (HIGH PERFORMANCE) |
| | |
| | #4 SHOW A 20' UTILITY EASEMENT OVER THE WATER MAIN |
| | COVERING FROM THE POINT IT ENTERS PROPERTY UP TO AND |
| | INCLUDING THE THE 4'X6' METER VAULT. |
| | (BACKFLOW IS PRIVATE, THERE FORE DO NOT INCLUDE INSIDE |
| | THIS EASEMENT.) SHEET 700-CO-017 |
| | |
| | #5 SHOW VERTICAL CLEARANCE OR SEPARATION BETWEEN |
| | PROPOSED WATER AND EXISTING 4" FM. SHEET 700-CO-017 |
| | |
| | #6 4" FM SHOULD BE CALLED OUT AS "EXIST. 4" FM" |
| | |
| | #7 VERIFY LOCATION FOR EXISTING 4" FM, PLANS SHOWS IT |
| | BEING INSIDE OF YOUR PROPERTY. IF THIS IS TRUE THEN |
| | PROVIDE LAYOUT OF FM ACROSS YOUR PROPERTY AND SUPPLY |
| | EASEMENT INFORMATION. |
| | |
| | #8 WATER AND SEWER WILL NEED TO BE SUBMITTED TO PBC |
| | HEALTH DEPARTMENT. |
| | |
| | #9 COST ESTIMATE SHOULD BE REVISED TO INCLUDE ELEMENTS |
| | THAT WILL REMAIN FOR THE PERMANENT PHASE. PLEASE |
| | REVISE. |
| | |
| | #10 OBTAIN ROW PERMIT FOR WORK WITHIN JOG RD. JOG RD IS |
| | A PALM BEACH COUNTY ROADWAY. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT |
| | MY OFFICE. THANK YOU! |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |