| 2011-02-15 14:11:21 | ENGINEERING SERVICES REVIEW COMMENTS: |
| | |
| | #1 REVIEW CONSISTS OF AVAILABILITY OF WATER AND SEWER |
| | FOR THE RUBBER DUCKY CAR WASH. |
| | -EXISTING WATER SERVICE HAS BEEN DETERMINED TO BE |
| | INADEQUATE AS TO THE DEMAND CALCULATED AND SUBMITTED BY |
| | ENGINEER OF RECORD. |
| | -EXISTING SEWER SERVICE HAS BEEN DETERMINED TO BE |
| | INADEQUATE AS TO THE DEMAND AND STANDARD REQUIRED BY |
| | CITY OF WEST PALM BEACH IMPOSED ON IMPACT OF NEW |
| | DEVELOPMENT. |
| | |
| | #2 SIDEWALKS AND ENTRANCE DRIVES WILL REMAIN IN THE |
| | SAME LOCATION. ANY PORTION OF WORK REQUIRING ANY CHANGE |
| | SHALL BE SUBMITTED FOR PERMIT TO THE FDOT OFFICE. THESE |
| | WILL ALSO CONSTITUTE A REVISION WITH THE ENGINEERING |
| | DEPARTMENT AND/OR PLANNING DEPARTMENT. |
| | |
| | #3 ENGINEERING DEPARTMENT HAS BEEN IN CONTACT WITH THE |
| | OWNER AND OR ENGINEER TO DETERMINE HOW TO BEST SERVE |
| | THE PROPERTY. UPON RECEIVING INFORMATION ON FLOW IT WAS |
| | DETERMINED BY CITY STAFF THAT A MINIMUM OF 2" SERVICE |
| | LINE WOULD BE REQUIRED. UPON RECEIVING THE FDOT |
| | DOCUMENTATION FROM THE EOR THE FOLLOWING COMMENTS WHERE |
| | GENERATED VIA E-MAIL, PLEASE SUBMIT: |
| | -ENGINEER'S COST ESTIMATE FOR THE WORK ** |
| | -SURETY. - THIS ESTIMATE MUST ACCOMPANY PERMIT ALONG |
| | WITH PROPER SURETY (110% OF THE COST OF CONSTRUCTION |
| | (FORMS WHERE ATTACHED). |
| | -SHOW AND INCLUDE SEWER UPGRADE. THIS WOULD INCLUDE A |
| | NEW 6" SEWER LATERAL FROM THE MAIN TO THE PROPERTY |
| | LINE. YOU HAVE IN PLACE AN OLD 4" CAST-IRON THAT WILL |
| | NOT SUFFICE YOUR DEVELOPMENT." |
| | |
| | #4 DRAINAGE SURFACE: EOR SUGGESTED USING A PERVIOUS |
| | TYPE CONCRETE SURFACE HOWEVER THIS TYPE PRODUCT IS NOT |
| | RECOGNIZED AS A FINISHED SURFACE PRODUCT BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | #5 PROVIDE SOUTH FLORIDA WATER MANAGEMENT APROVAL FOR |
| | SITE. |
| | |
| | #6 WATER WELL SYSTEM MUST HAVE PROPER VALVING AND |
| | BACKFLOW PREVENTION WHEN TIDE INTO CITY POTABLE WATER |
| | SERVICE. PLEASE PROVIDE A DETAIL ON THE PLANS WHERE |
| | THIS CONNECTION WILL BE MADE. AN AIR GAP MAY NEED TO BE |
| | PROVIDED BETWEEN THE TWO. SUBMIT SFWMD PERMIT APPROVAL |
| | AND FLOW CAPACITY INFORMATION. |
| | |
| | #7 A QUOTE FOR SERVICES WILL BE PROVIDED UPON APPROVAL |
| | OF POTABLE WATER SIZE. CONTRACTOR IS TO CONNECT SERVICE |
| | AT HIS EXPENSE. |
| | |
| | #8 ** SUBMIT A CERTIFIED COST ESTIMATE FOR ALL SITE |
| | DEVELOPMENT INFRASTRUCTURE. THIS DOCUMENT IS A |
| | REQUIREMENT OF YOUR SUBMITTAL TO ENGINEERING SERVICES |
| | DEPARTMENT. |
| | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP |
| | "AUTOCALC CERTIFIED COST ESTIMATE" |
| | |
| | #9 SURETY FOR INFRASTRUCTURE ELEMENTS WILL APPLY IF ANY |
| | WORK IN THE ROAD R.O.W. IS PERFORMED. |
| | |
| | PLEASE RESPOND TO ALL COMMENTS IN WRITING AND REVISE |
| | PLANS ACCORDINGLY. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |