| 2010-09-28 15:46:33 | FAILED: |
| | |
| | #1 TRUNCATED DOMES MISSING IN CRITICAL AREAS PLEASE |
| | REVISE PER MARK-UP. (SEE C2.1) |
| | #2 CLEAN UP C1.1 AS MARKED (ANY WORK TO BE PERFORMED IN |
| | WINDSOR AVE ROW WILL REQUIRE A ROW PERMIT. |
| | SEE INTERNET LINK: |
| | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP |
| | SEE ROW PARMIT APPLICATION DOCUMENT |
| | #3 DCDA FOR FIRELINE NEEDS TO BE AT PROPERTY LINE. (SEE |
| | C5.1) |
| | #4 FIRE HYDRANT ON-SITE WILL BE CONSIDERED "PRIVATE", |
| | YOU MAY BE REQUIRED TO INSTALL NEW HYDRANT AT PROPERTY |
| | LINE IF CLOSEST HYDRANT IS MORE THAT 150' FROM FDC |
| | LOCATION. |
| | #4A CITY STANDARD DETAIL P-8 IS MISSING. AFTER |
| | REVISION, FIRE MARSHALL MUST APPROVE PLAN PRIOR TO |
| | ENGINEERING PASS. |
| | #5 HYDRANT TEST REQUIRED AT NEAREST FIRE HYDRANT AS |
| | PART OF THE NEXT REVISION SUBMITTAL. |
| | TEST CAN BE SCHEDULED THRU THE CITY OF WPB FIRE |
| | MARSHALL'S OFFICE (561) 822-1200. |
| | #6 PARKING COUNT IN PARKING AREA CLOSES TO WINDSOR |
| | AVENUE IS LOWER THAN SHOWN. RECOUNT SPACES. SHT C2.1 |
| | #8 ENTRANCE AT 45TH STREET NEEDS TO BE CLARIFIED OR |
| | STRIPED TO ACCOMODATE TRAFFIC OPERATION. 1 DRIVE IN 1 |
| | DRIVE OUT. STRIPPING NEEDS TO BE WITHIN A CERTAIN WIDTH |
| | TO AVOID TWO VEHICLES EXITING AT THE SAME TIME. |
| | ANY CHANGES FROM THE 1 DRIVE IN AND 1 DRIVE OUT PATTERN |
| | SHOULD BE DISCUSSED WITH PALM BEACH COUNTY ROADWAY. |
| | #9 TRUNCATED DOMES AND ADA WILL BE REQUIRED AS THE |
| | DRIVEWAY IS PART OF YOUR DESIGN RESPONSABILITY. |
| | (DEPARTMENT OF JUSTICE, ADA |
| | ACCESSIBILITY GUIDELINES -ADAAG, ACCESSIBLE |
| | RIGHTS-OF-WAY, CHAPTER 3, SUBSECTION |
| | 3.2) |
| | #10 STRIPPING HAS BEEN MARKED UP ON SHEET C2.1 |
| | #11 SHEET C3.1 (NEEDS TO REFLECT PERVIOUS AND |
| | IMPERVIOUS AREAS. TOTAL SITE SF. ALSO) |
| | #12 CITY STANDARD TAPPING VALVE DETAIL IS MISSING. |
| | #13 POLLUTION PREVENTION PLAN MISSING WITH DETAILS. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |