2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENTMAINS. RATING NEEDS TO BE
 ABLE TO HANDLE AVAILABLE FAULT CURRENT.
 110-9/230-65
  
 2))NOTE:SHOW DISCONNECTS REQ`D FOR A/C
 PER 440-11
  
 3)NOTE: MASTER BEDROOM NEEDS TO HAVE
 MEANS OF EGRESS LIGHTING AS PER 210-70A
 AN ALSO FROM FAMILY ROOM GOING OUTSDIE.
  
 4)NOTE:NEED TO CHECK FOR KITCHEN PENIN-
 SULAR REQ`D RECEPT.PER 210-52-C
  
 5)NOTE: ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECT-
 ED. AS PER 210-8-A-6
  
 6)NOTE: NEED TO LABEL ALL OUTLETS THAT
 ARE REQ`D TO BE GFI/ GFI PROTECTED.
 GARAGE,OUTSIDE,BATHS AS PER 210-8
  
 7)NOTE: YOU SHOW EQUIPMENT GROUNDING
 CONDUCTOR BEING INSTALLED FROM METER
 TO PANELS?? ONLY AFTER FIRST MEANS
 OF DISC.
  
 8)NOTE:NOTE MISSING RECEPTS AS REQ`D BY
 210-52 2`6`12` RULE.
  
 9)NOTE:SMOKE DETECTORS INSTALLED INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D
 BY 1993/1996 NFPA-72 2-2.1.1.1
  
 10)NOTE: NEED TO HAVE COLD WATER PIPE,
 AND BLDG. STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. AS PER 250-81
 PLEASE SHOW ON RISER DIAGRAM 215-5
  
 11)NOTE:PLEASE SHOW ON PANEL SCHEDULES
 THE REQ`D BATH(S) CIRCUT(S) AS PER ART
 210-52D. NEED TO BE 20AMP #12 AWG.
  
 12)NOTE PLEASE INDICATE WHEATER OR NOT
 MAIN CIRCUT BRKR. PANELS OR NOT.215-5
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT. 8372