| 2001-01-08 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: NEED TO SUBMIT AIC RATING OF |
| | EQUIPMENTMAINS. RATING NEEDS TO BE |
| | ABLE TO HANDLE AVAILABLE FAULT CURRENT. |
| | 110-9/230-65 |
| | |
| | 2))NOTE:SHOW DISCONNECTS REQ`D FOR A/C |
| | PER 440-11 |
| | |
| | 3)NOTE: MASTER BEDROOM NEEDS TO HAVE |
| | MEANS OF EGRESS LIGHTING AS PER 210-70A |
| | AN ALSO FROM FAMILY ROOM GOING OUTSDIE. |
| | |
| | 4)NOTE:NEED TO CHECK FOR KITCHEN PENIN- |
| | SULAR REQ`D RECEPT.PER 210-52-C |
| | |
| | 5)NOTE: ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECT- |
| | ED. AS PER 210-8-A-6 |
| | |
| | 6)NOTE: NEED TO LABEL ALL OUTLETS THAT |
| | ARE REQ`D TO BE GFI/ GFI PROTECTED. |
| | GARAGE,OUTSIDE,BATHS AS PER 210-8 |
| | |
| | 7)NOTE: YOU SHOW EQUIPMENT GROUNDING |
| | CONDUCTOR BEING INSTALLED FROM METER |
| | TO PANELS?? ONLY AFTER FIRST MEANS |
| | OF DISC. |
| | |
| | 8)NOTE:NOTE MISSING RECEPTS AS REQ`D BY |
| | 210-52 2`6`12` RULE. |
| | |
| | 9)NOTE:SMOKE DETECTORS INSTALLED INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D |
| | BY 1993/1996 NFPA-72 2-2.1.1.1 |
| | |
| | 10)NOTE: NEED TO HAVE COLD WATER PIPE, |
| | AND BLDG. STEEL AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. AS PER 250-81 |
| | PLEASE SHOW ON RISER DIAGRAM 215-5 |
| | |
| | 11)NOTE:PLEASE SHOW ON PANEL SCHEDULES |
| | THE REQ`D BATH(S) CIRCUT(S) AS PER ART |
| | 210-52D. NEED TO BE 20AMP #12 AWG. |
| | |
| | 12)NOTE PLEASE INDICATE WHEATER OR NOT |
| | MAIN CIRCUT BRKR. PANELS OR NOT.215-5 |
| | |
| | NEED TO SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND APPROVAL. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL 659-8096 |
| | EXT. 8372 |