Plan Review Notes
Plan Review Notes For Permit 99122063
Permit Number 99122063
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************ UNSAT *********************
  
 1)NOTE:MISSING WP GFI OUTLET AS REQ`D
 BY ART;210-52E OF THE NEC BACK OF NEW
 ADDIDTION.
  
 2)NOTE: NEW ADDITION BATH GFI OOUTLET IS
 TO BE LISTED ON PANEL SCHEDULE AS 20AMP
 #12 AS REQ`D BY 210-52D/215-5
  
 3)NOTE:GROUNDING ELECTRODE CONDUCTOR
 IS TO GO TO BLDG.STEEL OF NEW ADDITION
 AS REQ`D BY 250-81 OF THE NEC.
  
 4)NOTE:RISER DIAGRAM SHOWS 18 POLE
 MCB PANEL??? YET PANEL SCHEDULE HAS MORE
 BRKRS/CIRCUTS THAN WILL FIT.PLEASE
 CHANGE.
  
 5)NOTE: LOAD FOR GEN LIGHTING NEEDS TO
 BE BY TOTAL AREA OF LIVING AREAS. 3 VA
 PER SQ FT.
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS CALL 659-8096 EXT 8372