| Plan Review Notes For Permit 99122063 |
| Permit Number |
99122063 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************ UNSAT ********************* | | | | | | 1)NOTE:MISSING WP GFI OUTLET AS REQ`D | | | BY ART;210-52E OF THE NEC BACK OF NEW | | | ADDIDTION. | | | | | | 2)NOTE: NEW ADDITION BATH GFI OOUTLET IS | | | TO BE LISTED ON PANEL SCHEDULE AS 20AMP | | | #12 AS REQ`D BY 210-52D/215-5 | | | | | | 3)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | IS TO GO TO BLDG.STEEL OF NEW ADDITION | | | AS REQ`D BY 250-81 OF THE NEC. | | | | | | 4)NOTE:RISER DIAGRAM SHOWS 18 POLE | | | MCB PANEL??? YET PANEL SCHEDULE HAS MORE | | | BRKRS/CIRCUTS THAN WILL FIT.PLEASE | | | CHANGE. | | | | | | 5)NOTE: LOAD FOR GEN LIGHTING NEEDS TO | | | BE BY TOTAL AREA OF LIVING AREAS. 3 VA | | | PER SQ FT. | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL. IF THERE ARE ANY | | | QUESTIONS CALL 659-8096 EXT 8372 |
|