Plan Review Notes
Plan Review Notes For Permit 99122041
Permit Number 99122041
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE BATHROOM WITH A DOOR
 HAVING A MINIMUM OF 29" CLEAR OPENING.
 SECTION 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION,1997.
 2-PROVIDE PRODUCT APPROVAL FOR SLIDING
 WINDOWS.
 RE-SUBMIT OTHER PRODUCT APPROVALS. SEE
 COMMENTS.
 3-REVISE SIZE OF EGRESS WINDOW AT
 BEDROOM #3. MINIMUM NET CLEAR OPENING
 TO BE 5.7 SQ. FT. SEC. 1005.4 SBC/1997
 4-PROVIDE COMPLETE FRAMING DETAILS FOR
 ARCHED OPENINGS.
 5-SEE ALL COMMENTS ON PLANS AND REVISE/
 UPDATE ALL DRAWINGS AS REQUIRED.
 RE-SUBMIT PRIOR TO INSPECTIONS.
 6-ATTIC ACCESS TO BE 22" X 36" MIN.
 SECTION 2309.6 SBC 1997.
 7-PROVIDE DRAFSTOPPING AT SECOND FLOOR
 FRAMING PLAN. SEE SEC.2305.2 SBC/1997.
 8-COMPLY WITH PROVISOS BY OTHER TRADES.
 9-PROVIDE PRODUCT APPROVAL FOR FLAT
 ROOF SYSTEM.
 10-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS AS PER SECTION 1606
 SBC 1997.