| Plan Review Notes For Permit 99122041 |
| Permit Number |
99122041 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SHOW MAIN DISC ON PLANS | | | 215-5 | | | | | | 2)NOTE:210-8-A-6 ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE ARE TO BE GFI/GFI | | | PROTECTED. PLEASE SHOW. | | | | | | 3)NOTE:PANEL SHOWS 48 POLES. NOTE 384-15 | | | 42 CIRCUT.MAX | | | | | | 4)NOTE:YOU SHOW ON RISER DIAGRAM TWO | | | SETS OF WIRES FOR PANEL FEEDS.?? | | | PLEASE CLARIFY. | | | | | | 5)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS AS REQ`D | | | BY NFPA-72 2-2.1.1.1 | | | | | | 6)NOTE:AS REQ`D BY 210-63 OF THE NEC. | | | AN OUTLET IS REQ`D FOR AHU UNIT IN THE | | | ATTIC. DO NOT LIST AS OPTIONAL. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT | | | 8372 |
|