| Plan Review Notes For Permit 99122031 |
| Permit Number |
99122031 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE "A0" . PROVIDE ELEVATION | | | CERTIFICATE. | | | 2-SHEET A-1: TYPICAL EXTERIOR CEILING | | | DETAIL. SEE STANDARDS ASTM C926 AND | | | ASTM C1063, THEN SPECIFY CONSTRUCTION | | | OF CEILING AT ENTRY AND REAR PORCH. | | | TABLE 2506 OF SBC 1997 APPLIES FOR | | | SHEARWALLS NOT FOR CEILINGS. | | | 3-ENGINEER OF RECORD TO PROVIDE THE | | | CALCULATED DESIGN PRESSURES AT ALL | | | EXTERIOR OPENINGS IN ORDER TO BE | | | CERTAIN IF PRODUCT APPROVALS HAVE THE | | | REQUIRED DESIGN PRESSURES. | | | 4-PROVIDE PRODUCT APPROVAL FOR "INSWING" | | | ENTRY DOOR AS SHOWN ON PLANS. | | | 5-PROVIDE PRODUCT APPROVAL FOR FLAT | | | ROOF SYSTEM. | | | 6-PROVIDE COPIES OF TEST RESULTS FOR | | | SLIDING GLASS DOORS AS PER ASTM E-330. | | | SECTION 1706 SBC 1997. | | | 7-PROVIDE SMOKE DETECTOR ON FIRST FLOOR | | | BY THE STAIRS. SEC 905.2.2 SBC 1997. | | | 8-SEE COMMENTS ON PLANS AND REVISE/ | | | UPDATE DRAWINGS. | | | 9-PROVIDE DRAFSTOPPING AT SECOND FLOOR | | | PLAN. SECTION 2305.2.2 SBC 1997. |
|