Plan Review Notes
Plan Review Notes For Permit 99122031
Permit Number 99122031
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0" . PROVIDE ELEVATION
 CERTIFICATE.
 2-SHEET A-1: TYPICAL EXTERIOR CEILING
 DETAIL. SEE STANDARDS ASTM C926 AND
 ASTM C1063, THEN SPECIFY CONSTRUCTION
 OF CEILING AT ENTRY AND REAR PORCH.
 TABLE 2506 OF SBC 1997 APPLIES FOR
 SHEARWALLS NOT FOR CEILINGS.
 3-ENGINEER OF RECORD TO PROVIDE THE
 CALCULATED DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS IN ORDER TO BE
 CERTAIN IF PRODUCT APPROVALS HAVE THE
 REQUIRED DESIGN PRESSURES.
 4-PROVIDE PRODUCT APPROVAL FOR "INSWING"
 ENTRY DOOR AS SHOWN ON PLANS.
 5-PROVIDE PRODUCT APPROVAL FOR FLAT
 ROOF SYSTEM.
 6-PROVIDE COPIES OF TEST RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM E-330.
 SECTION 1706 SBC 1997.
 7-PROVIDE SMOKE DETECTOR ON FIRST FLOOR
 BY THE STAIRS. SEC 905.2.2 SBC 1997.
 8-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE DRAWINGS.
 9-PROVIDE DRAFSTOPPING AT SECOND FLOOR
 PLAN. SECTION 2305.2.2 SBC 1997.