Plan Review Notes
Plan Review Notes For Permit 99121969
Permit Number 99121969
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY THE FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SEC.3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS IN THE COVERED DWELLING
 UNIT SHALL COMPLY W/THE PROVISIONS OF
 THE FEDERAL FAIR HOUSING ACT 24 CFR
 100.205 (C)(3)(IV) REQUIREMENT #7 (2)
 PARAGRAPH (A)OR(B).CLEAR FLOOR SPACE
 SHALL BE PROVIDED AT FIXTURES TO ALLOW A
 PERSON IN A WHEELCHAIR OR OTHER MOBILITY
 AID USE OF THE FIXTURES.CLEAR FLOOR
 SPACE SHALL BE SHOWN ON THE PLANS AND
 DESIGNATE WHICH OPTION OF REQUIREMENT#7
 (A OR B) IS BEING USED.
  
 LAUNDRY ROOMS SHALL COMPLY W/ANSI A117.1
 1986 SEC.4.32.1-4.32.6.3.
  
 ALL TOILET ROOMS AND BATHING FACILITIES
 IN ALL PUBLIC AND COMMON AREAS SHALL BE
 ACCESSIBLE PER ANSI A117.1 1986 SEC.
 4.22.1-4.22.4.
  
 SUBMIT SQUARE FOOTAGE OF REC.BUILDING
 AND OCCUPANT LOAD TO ENSURE COMPLIANCE
 W/SPC TABLE 407.
  
 SHT.A-4.2.1.-HANDICAP STALLS ARE UNDER-
 SIZED.COMPLY W/FACBC SEC.4.17.3
 EXCEPTION:NEW CONSTRUCTION.
  
 SHOW CLEAR FLOOR SPACE AT URINAL AND
 HEIGHT OF URINAL.COMPLY W/FACBC SEC.
 4.18.1 THRU 4.18.4.
  
 SUBMIT DETAILS/MOUNTING HEIGHTS OF ALL
 PLUMBING FIXTURES/APPURTENANCES.COMPLY
 W/FACBC AND SPC 403.4.
  
 SHT.P-1-CLEANOUTS SHALL BE INSTALLED
 IN BUILDING DRAIN AND COMPLY W/SPC SEC.
 710.2.4.
  
 SUBMIT RISER DIAGRAM FOR COMPLETE STORM
 WATER SYSTEM.SUBMIT DETAILS/CALCULATIONS
 FOR SECONDARY DRAINAGE PER SPC 1109.1,
 1109.2,APPENDIX"A"& TABLE A101.2.
  
 DETAIL THE TYPE OF OPERATIONS TO BE
 CONDUCTED IN THE KITCHEN.IF FOOD WILL BE
 COOKED A GREASE INTERCEPTOR WILL BE REQD
 PER SPC 1OO4.1.SUBMIT DETAIL OF GREASE
 TRAP.SPC 1004.2.
  
 SIZE THE UNDERGROUND SANITARY SYSTEM
 IN ITS ENTIRETY.COMPLY W/SPC SEC.714.1,
 714.2.
  
 SIZE THE WATER RISERS ON SHT.P-8.COMPLY
 W/SPC SEC.607.1,APPENDIX"F".
  
 WATER SUPPLY BRANCHES TO KIT.SINKS SHALL
 BE VALVED PER SPC SEC.610.4.1.
  
 SHT.P-9-VERTICAL COMBINATION WASTE AND
 VENT SYSTEM FOR KIT.SINK.SHALL COMPLY W/
 SPC SEC.911.4.AND TABLE 911.4.(SEE
 RISERS S2,S3,S5,S6,S7,S9.
  
 SANITARY RISERS S1,S4,S5,S8-SHALL COMPLY
 W/SPC SEC.911.3.(SIZE OF LOWEST WET VENT
  
 P & T DRAINS SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6(3).
 (DISCHARGE TO EXTERIOR).
  
 CLARIFY TYPE OF DRAINS FOR WASHING
 MACHINES.DESIGN IS UNFAMILIAR AND DOES
 NOT APPEAR TO COMPLY W/SPC.