| Plan Review Notes For Permit 99121969 |
| Permit Number |
99121969 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************DENIED********************** | | | | | | 1. ALL DUCTS TO HAVE FIRE DAMPERS AT | | | SHAFTWALL PENETRATION PER 1997 SMC 610.1 | | | 2. DRYER VENT DUCTS TO BE MIN. 26 GA. | | | AND SHALL RUN FULL LENGTH TO OUTSIDE OF | | | BUILDING AND NOT TERMINATE INTO CONCEAL- | | | ED SHAFT.SUBDUCT NOT ALLOWED FOR DRYER | | | VENTS.SMC 509 | | | 3. PROVIDE RISER SHOWING BATH EXHAUST | | | SUBDUCT AND SHAFT | | | 4. PROVIDE DUCT SIZE FROM 16X10 TO 4" & | | | 8" @ TRIANGLE BOX ON 2ND BEDROOM PLAN | | | 5. SHOW HEIGHT OF INTAKE LOUVER OVER | | | CONDENSER UNITS- OUTSIDE AIR INTAKE IS | | | ONLY 2' FROM CONDENSING UNITS PER PLAN | | | 6. OVERFLOW PROTECTION REQUIRED ON ALL | | | AHU'S. 1997 SMC 304.8.6 | | | 7. PROVIDE INFORMATION ON FLUE VENT | | | (DETAIL AND ROOF TERMINATION) FOR GENER- | | | ATOR |
|