2001-01-08 00:00:00************DENIED**********************
  
 1. ALL DUCTS TO HAVE FIRE DAMPERS AT
 SHAFTWALL PENETRATION PER 1997 SMC 610.1
 2. DRYER VENT DUCTS TO BE MIN. 26 GA.
 AND SHALL RUN FULL LENGTH TO OUTSIDE OF
 BUILDING AND NOT TERMINATE INTO CONCEAL-
 ED SHAFT.SUBDUCT NOT ALLOWED FOR DRYER
 VENTS.SMC 509
 3. PROVIDE RISER SHOWING BATH EXHAUST
 SUBDUCT AND SHAFT
 4. PROVIDE DUCT SIZE FROM 16X10 TO 4" &
 8" @ TRIANGLE BOX ON 2ND BEDROOM PLAN
 5. SHOW HEIGHT OF INTAKE LOUVER OVER
 CONDENSER UNITS- OUTSIDE AIR INTAKE IS
 ONLY 2' FROM CONDENSING UNITS PER PLAN
 6. OVERFLOW PROTECTION REQUIRED ON ALL
 AHU'S. 1997 SMC 304.8.6
 7. PROVIDE INFORMATION ON FLUE VENT
 (DETAIL AND ROOF TERMINATION) FOR GENER-
 ATOR