| Plan Review Notes For Permit 99121969 |
| Permit Number |
99121969 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-ALL BRANCH CIRCUIT NUMBERS TO BE | | | SHOWN ON PLAN FOR # OF OUTLETS AND | | | LIGHTS PER CIRCUIT. | | | | | | 2-NEED TO SHOW LOCATION OF ALL EQUIPME | | | UNITS DO NOT SHOW WATERHEATER AND | | | AIRHANDLER LOCATIONS. | | | | | | 3-2 BEDROOM UNIT SHOWS WASHER AND | | | DRYER ON LOAD CALCULATION BUT NOT ON | | | PLANS. | | | | | | 4-NO PANEL SCHEDULES SHOWN FOR 1 AND 2 | | | BEDROOM UNITS. | | | | | | 5-NO WIRE SIZES SHOWN FOR THE MAINS | | | OUT TO FPL. | | | | | | 6-PANEL SCHEDULS FOR THE UNITS NEEDED | | | SHOW SIZE, AIC RATING,CIRCUIT NUMBER | | | | | | 7-PROVIDE ALL THE ABOVE INFORMATION | | | PRIOR TO THE FIRST ELCTRICAL ROUGH | | | INSPECTION. |
|