Plan Review Notes
Plan Review Notes For Permit 99121955
Permit Number 99121955
Review Stop R
Sequence Number 3
Notes
Date Text
2001-02-14 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1-TRUSS DRAWINGS STILL SHOW THE WRONG
 MEAN ROOF HEIGHT. THIS IS A TWO STORY
 BUILDING. THEREFORE, MEAN ROOF HEIGHT
 IS +/- 23'-8". REVISE AS REQUIRED.
 2-SBC 1997 DOESN'T USE "WALL HEIGHT". IT
 USES THE MEAN ROOF HEIGHT OF THE
 BUILDING. REVISE AS REQUIRED.
 3-CHECK IF CONNECTORS SPECIFIED WILL
 RESIST THE LOADS CALCULATED ON THE
 REVISED ENGINEERED TRUSS DRAWINGS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 4-UNABLE TO IDENTIFY ENGINEER.
 -ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND NUMBER ON EACH SHEET
 AS REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES.