| Plan Review Notes For Permit 99121955 |
| Permit Number |
99121955 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. MAINS TO BE RATED FOR | | | AVAILABLE FAULT CURRENT.AS REQ`D BY ARTS | | | 110-9/110-10/215-5 O FTHE NEC. | | | | | | 2)NOTE:SHOW DISC. FOR A/C COND.UNIT | | | AS PER 440-11/215-5 | | | | | | 3)NOTE: SHOW MAIN DISC. ON PLANS BY | | | METER AS SHOWN ON RISER DIAGRAM. | | | | | | 4)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | | | | 5)NOTE:ALL OUTLETS SERVING KITCHEN | | | COUNTER SPACE ARE TO BE GFI/GFI PROTECT- | | | -ED. AS PER 210-8-A-6 | | | | | | 6)NOTE:PLEASE SHOW THE DEDICATED CIRCUT | | | FOR THE BATH(S) AS REQ`D BY 210-52D | | | MUST BE 20AMP # 12 AWG. PLEASE LIST ON | | | PANEL SCHEDULE. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROAVL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 X8372 |
|