| Plan Review Notes For Permit 99121922 |
| Permit Number |
99121922 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE A8. NEED TO PROVIDE | | | ELEVATION CERTIFICATE. | | | 2-ENERGY CALCULATIONS NEED TO BE REVISED | | | SHOWING THE ACTUAL CONDITIONED FLOOR | | | AREA (2749 S.F.). THIS CAN'T BE DONE | | | MANUALLY. IT'S A COMPUTER PROGRAM. | | | 3-AREA CALCULATIONS TO BE REVISED IN | | | ORIGINAL DRAWING BY THE ENGINEER OF | | | RECORD. HE'S THE ONE RESPONSIBLE TO DO | | | ANY CHANGES IN HIS DRAWINGS. | | | 4-PROVIDE COPIES OF NORANDEX SLIDING | | | GLASS DOORS SHOWING TESTS RESULTS DONE | | | AS PER ASTM E-330. |
|