| Plan Review Notes For Permit 99121922 |
| Permit Number |
99121922 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED. | | | | | | 2)ADDITIONAL IMPACT FEES ARE DUE TO THE | | | COUNTY FOR ADDITIONAL 397 SQFT UNDER A/C | | | FOR OPTIONAL LOFT AND NOOK OFF KITCHEN. | | | | | | 3)SUBMIT 2 COPIES OF REVISED STORM PANEL | | | KEY PLAN AND SCHEDULE THAT CORRESPONDS | | | WITH SPECIFIC OPTIONS TO BE USED. | | | | | | 4)SPECIFICATIONS FOR GARAGE DOOR | | | SUBMITTED WITH PRODUCT APPROVAL INDICATE | | | A NEGATIVE DESIGN PRESSURE OF -33PSF FOR | | | A 16'X7' DOOR ,WIND LOADS ON SHEET A-4A | | | LISTS NEG. PRESSURE OF -34PSF. | | | PLEASE CORRECT. | | | | | | 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE | | | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR | | | OUTSWING STEEL DOOR WITH SIDE LITES AS | | | SHOWN ON PLANS.PRODUCT APPROVALS ARE | | | REQUIRED FOR SPECIFIC ITEM THAT WILL BE | | | INSTALLED. | | | | | | 6)THE VALUES LISTED IN THE WIND PRESSURE | | | SCHEDULE ON SHEET A-4A DO NOT AGREE WITH | | | THE PRESSURES LISTED ON THE DRAWING FOR | | | WINDOWS J,S & T. PLEASE CORRECT. |
|