| Plan Review Notes For Permit 99121905 |
| Permit Number |
99121905 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO ************** | | | | | | 1)NOTE:PLEASE NOTE THAT YOU HAVE A 52AMP | | | LOAD ON PANEL B AND YOU SHOW A 2P-40 | | | FEEDING THAT PANLE.ALSO PLEASE NOTE THAT | | | AS PER 310-16 #8 IN THE 75C COLUMN IS | | | ONLY RATED FOR 50 AMPS. CANNOT USE THE | | | 90C RATING. | | | | | | PLEASE CORRECT THE ABOVE AND SUBMIT FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|