| Plan Review Notes For Permit 99121883 |
| Permit Number |
99121883 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | 1-PROVIDE ATTIC ACCESS AT ROOF ABOVE | | | GARAGE. SECTION 2309.6 SBC 1997. | | | 2-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE PLANS FOR COMMENTS. | | | 3-FLOOD ZONE "A8" PROVIDE ELEVATION | | | CERTIFICATE. | | | 4-STAIRS DETAIL: CLARIFY TREAD TO RISER | | | RATIO, SEC. 1007.3 SBC 1997. | | | -PROVIDE FIREBLOCKING SEC 2305 SBC/1997 | | | 5-PROVIDE LEGIBLE AND COMPLETE PRODUCT | | | APPROVALS FOR ENTRY DOOR AND GARAGE | | | DOOR. | | | 6-SECOND FLOOR BEDROOM WINDOWS TO COMPLY | | | WITH SECTION 1005.4 SBC 1997 BY HAVING | | | A MINIMUM CLEAR OPENING OF 5.7 SQ. FT. | | | AND A MINIMUM CLEAR HEIGHT OPENING | | | OF 24". | | | NOTE: REVISE FLOOR PLAN TO CLARIFY THE | | | SIZE OF WINDOW AND MASONRY OPENING. | | | THEY DON'T MATCH. | | | 7-PROVIDE COMPLETE DETAILS FOR ROUND | | | OPENINGS AT WOOD FRAMING WALL. | | | 8-ATTIC ACCESS AT MASTER BEDROOM CLOSET | | | TO BE 22"X36" MIN. SEC 2309.6 SBC/97. | | | 9-PROVIDE DRAFSTOPPING AT SECOND FLOOR | | | FRAMING PLAN. INDICATE LOCATION AND | | | MATERIAL AS PER SECTION 2305.2 SBC/97. |
|