2001-01-08 00:00:00PROVISO:
  
 1-PROVIDE ATTIC ACCESS AT ROOF ABOVE
 GARAGE. SECTION 2309.6 SBC 1997.
 2-UPDATE/REVISE ALL DRAWINGS AS REQUIRED
 SEE PLANS FOR COMMENTS.
 3-FLOOD ZONE "A8" PROVIDE ELEVATION
 CERTIFICATE.
 4-STAIRS DETAIL: CLARIFY TREAD TO RISER
 RATIO, SEC. 1007.3 SBC 1997.
 -PROVIDE FIREBLOCKING SEC 2305 SBC/1997
 5-PROVIDE LEGIBLE AND COMPLETE PRODUCT
 APPROVALS FOR ENTRY DOOR AND GARAGE
 DOOR.
 6-SECOND FLOOR BEDROOM WINDOWS TO COMPLY
 WITH SECTION 1005.4 SBC 1997 BY HAVING
 A MINIMUM CLEAR OPENING OF 5.7 SQ. FT.
 AND A MINIMUM CLEAR HEIGHT OPENING
 OF 24".
 NOTE: REVISE FLOOR PLAN TO CLARIFY THE
 SIZE OF WINDOW AND MASONRY OPENING.
 THEY DON'T MATCH.
 7-PROVIDE COMPLETE DETAILS FOR ROUND
 OPENINGS AT WOOD FRAMING WALL.
 8-ATTIC ACCESS AT MASTER BEDROOM CLOSET
 TO BE 22"X36" MIN. SEC 2309.6 SBC/97.
 9-PROVIDE DRAFSTOPPING AT SECOND FLOOR
 FRAMING PLAN. INDICATE LOCATION AND
 MATERIAL AS PER SECTION 2305.2 SBC/97.