2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 MAINS. MAINS NEED TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT.AS REQ`D BY
 ARTS:110-9/110-10/215-5
  
 2)NOTE: SHOW A/C DISC.REQ`D BY 440-11
 OF THE NEC.
  
 3)NOTE: NEED TO SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. AS PER ART:210-8-A-6
  
 4)NOTE: NEED TO HAVE THE DEDICATED CIR-
 -CUT(S) FOR THE BATH(S) AS REQ`D BY
 ART:210-52D THEY MUST BE 20AMP AND #12
 AWG.
  
 5)NOTE: PLEASE SHOW ON PLANS MAIN DISC.
 AS SHOWN RISER DIAGRAM.
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372