| Plan Review Notes For Permit 99121883 |
| Permit Number |
99121883 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | MAINS. MAINS NEED TO BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.AS REQ`D BY | | | ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE: SHOW A/C DISC.REQ`D BY 440-11 | | | OF THE NEC. | | | | | | 3)NOTE: NEED TO SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. AS PER ART:210-8-A-6 | | | | | | 4)NOTE: NEED TO HAVE THE DEDICATED CIR- | | | -CUT(S) FOR THE BATH(S) AS REQ`D BY | | | ART:210-52D THEY MUST BE 20AMP AND #12 | | | AWG. | | | | | | 5)NOTE: PLEASE SHOW ON PLANS MAIN DISC. | | | AS SHOWN RISER DIAGRAM. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|