| Plan Review Notes For Permit 99121865 |
| Permit Number |
99121865 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-02 00:00:00 | ***************PROVISO****************** | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) PROVIDE FLOOD ZONE ELEVATION | | | CERTIFICATE FOR NEW CONSTRUTION WITH BFE | | | | | | 3) PROVIDE PRODUCT APPROVAL FOR OVERHEAD | | | GARAGE DOOR THAT HAS DESIGN LOADS WHICH | | | EQUAL OR EXCEED THE CALCULATED WINDLOADS | | | FOR THE GARAGE OPENING OF THE STRUCTURE. | | | | | | 4) PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ARCHED FIXED GLASS WINDOWS | | | - STRUCTURAL WINDOW MULLIONS | | | | | | 5)WINDOW PRESSURE SCHEDULE VALUES FOR | | | WINDOWS J,S AND T DO NOT CORRESPOND WITH | | | THE PRESSURES LISTED ON THE DRAWINGS. | | | SUBMIT REVISED SCHEDULE OR REVISED SHEET | | | A-4A. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|