2001-01-08 00:00:00**************** PROVISO **************
  
 REVISE PLAN BEFORE FINAL!!!!
  
 1)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210-8-A-6
  
 2)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 PLAN THAT IS SHOWN ON RISER DIAGRAM.
  
 3)NOTE: PLEASE SEE RISER AND PANEL SCHED
 -ULE. ONE SHOWS MLO AND THE OTHER THE
 PANEL IS SHOWN AS MCB.
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR THE 28 CIRCUIT PANEL SHOWN. THIS
 DOES NOT SEEM TO BE A STANDARD SIZE PAN-
 -EL. 215-5
  
 5)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3 AND 215-5
  
 PLEASE REVISE AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW BEFORE FINAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372