| Plan Review Notes For Permit 99121858 |
| Permit Number |
99121858 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO ************** | | | | | | REVISE PLAN BEFORE FINAL!!!! | | | | | | 1)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. PER 210-8-A-6 | | | | | | 2)NOTE: PLEASE SHOW MAIN DISCONNECT ON | | | PLAN THAT IS SHOWN ON RISER DIAGRAM. | | | | | | 3)NOTE: PLEASE SEE RISER AND PANEL SCHED | | | -ULE. ONE SHOWS MLO AND THE OTHER THE | | | PANEL IS SHOWN AS MCB. | | | | | | 4)NOTE: PLEASE PROVIDE CLARIFICATION | | | FOR THE 28 CIRCUIT PANEL SHOWN. THIS | | | DOES NOT SEEM TO BE A STANDARD SIZE PAN- | | | -EL. 215-5 | | | | | | 5)NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3 AND 215-5 | | | | | | PLEASE REVISE AND SUBMIT ALL THE ABOVE | | | INFORMATION FOR REVIEW BEFORE FINAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|