| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: PLEASE NOTE AS PER 384-15 | | | YOU SHOW 48 POLES FOR PANEL??? | | | | | | 2)NOTE:AS REQ`D BY 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED.PLEASE SHOW!!! | | | | | | 3)NOTE: RISER SHOWS MAIN DISCONNECT. | | | PLEASE SHOW ON PLANS.215-5 | | | | | | 4) PLEASE INDICATE THE BATH(S) CIRCUT AS | | | REQ`D BY 210-11-C-3 | | | | | | PLEASE HAVE ALL THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE ANY ELEC. | | | INSPECTION IS CALLED IN. |
|