2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT PLANS SHOWING
 AIC RATING OF MAINS. MAIN IS TO BE
 RATED FOR AVAILABLE FAULT CURRENT.
 AS REQ`D BY ARTS:110-9/110-10/215-5
  
 2) NOTE: RISER SHOWS MAIN,,,PLEASE SHOW
 ON PLANS NEXT TO METER.
  
 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED.AS REQ`D BY ART:210-8-A-6 OF THE
 NEC.
  
 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. IF THERE
 IS A OPTIONAL DEN PLEASE SHOW AS OPT.
  
 5)NOTE:PLEASE LIST THE DEDICATED BATH(S)
 CIRUCT(S) ON PANEL SCHEDULE. AS REQ`D
 BY 210-52. MUST BE 20AMP AND #12 AWG.
  
 PLEASE HAVE ALL THE ABOVE INFORMAITON
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372