| Plan Review Notes For Permit 99121824 |
| Permit Number |
99121824 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT PLANS SHOWING | | | AIC RATING OF MAINS. MAIN IS TO BE | | | RATED FOR AVAILABLE FAULT CURRENT. | | | AS REQ`D BY ARTS:110-9/110-10/215-5 | | | | | | 2) NOTE: RISER SHOWS MAIN,,,PLEASE SHOW | | | ON PLANS NEXT TO METER. | | | | | | 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED.AS REQ`D BY ART:210-8-A-6 OF THE | | | NEC. | | | | | | 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. IF THERE | | | IS A OPTIONAL DEN PLEASE SHOW AS OPT. | | | | | | 5)NOTE:PLEASE LIST THE DEDICATED BATH(S) | | | CIRUCT(S) ON PANEL SCHEDULE. AS REQ`D | | | BY 210-52. MUST BE 20AMP AND #12 AWG. | | | | | | PLEASE HAVE ALL THE ABOVE INFORMAITON | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|