| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SHOW AIC RATING OF | | | EQUIPMENT MAINS. MAINS NEED TO BE RATED | | | FOR AVAILABLE FAULT CURRENT. AS REQ`D | | | BY ARTS: 110-9/110-10/215-5 | | | | | | 2)NOTE:SHOW BLDG.STEEL ON PLANS. | | | | | | 3)NOTE:AS REQ`D BY 1993/1993 NFPA-72 | | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | | | | 4)NOTE: PLEASE SHOW ALL OUTLETS THAT | | | ARE SERVING KITCHEN COUNTER SPACE | | | AS GFI/GFI PROTECTED. | | | | | | 5)NOTE: PLEASE HAVE THE DEDICATED BATH(S | | | CIRCUT(S)LISTED ON PANEL SCHEDULE. | | | MUST BE 20AMP AND #12 AWG. AS REQ`D BY | | | ART:210-52D OF THE NEC. | | | | | | PLEASE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|