Plan Review Notes
Plan Review Notes For Permit 99121818
Permit Number 99121818
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SHOW AIC RATING OF
 EQUIPMENT MAINS. MAINS NEED TO BE RATED
 FOR AVAILABLE FAULT CURRENT. AS REQ`D
 BY ARTS: 110-9/110-10/215-5
  
 2)NOTE:SHOW BLDG.STEEL ON PLANS.
  
 3)NOTE:AS REQ`D BY 1993/1993 NFPA-72
 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
  
 4)NOTE: PLEASE SHOW ALL OUTLETS THAT
 ARE SERVING KITCHEN COUNTER SPACE
 AS GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE HAVE THE DEDICATED BATH(S
 CIRCUT(S)LISTED ON PANEL SCHEDULE.
 MUST BE 20AMP AND #12 AWG. AS REQ`D BY
 ART:210-52D OF THE NEC.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372