| Plan Review Notes For Permit 99121816 |
| Permit Number |
99121816 |
|
| Review Stop |
R |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-12 00:00:00 | TRUSSES CHECKLIST: | | | 1-WHERE IS THE ENGINEERING FOR THE | | | PARALAM BEAM? | | | 2-TRUSS DRAWINGS GENERAL DETAILS AND | | | SPECIFICATIONS PACKAGE NEED TO BE | | | COORDINATED AND UPDATED. THERE ARE | | | DETAILS AND SPECS THAT ARE TOO OLD AND | | | REFERENCING OLD CODES. | | | -WHY IS ENGINEER SIGNING AND SEALING | | | DOCUMENTS WITH THE NAME OF ANOTHER | | | ENGINEER? | | | -ENGINEER TO COMPLY WITH CHAPTER 471 | | | FL. STATUTES WHEN SUBMITTING ANY | | | INFORMATION FOR PUBLIC RECORDS. | | | 3-SUPPORT REPORT INDICATES THAT TRUSSES | | | WERE DESIGNED USING SBC 1991. | | | | | | | | | | | | | | | JULIO GOMEZ, BUILDING PLAN EXAMINER, | | | EXT. 8232. |
|