| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE "A0". PROVIDE ELEVATION |
| | CERTIFICATE AFTER SLAB IS POURED. |
| | 2-PRODUCT APPROVALS: |
| | -PROVIDE PRODUCT APPROVAL FOR TWO HOUR |
| | FIRE RATED CONCRETE BLOCK, EXTERIOR |
| | FRENCH DOOR WITH SIDELITES ASSEMBLY, |
| | EXTERIOR DOUBLE FRENCH DOOR, WINDOW |
| | MULLIONS. |
| | -DRAWINGS IN PRODUCT APPROVAL FOR THE |
| | SLIDING GLASS DOORS ARE NOT LEGIBLE. |
| | 3-PROVIDE BUCK DETAIL FOR SLIDING GLASS |
| | DOORS. SEC 104.2.2 CITY AMENDMENTS. |
| | 4-PRODUCT APPROVAL FOR SINGLE HUNG |
| | WINDOW REQUIRES A 2X BUCK. REVISE |
| | WINDOW BUCK DETAIL AS REQUIRED. |
| | 5-STORM PANELS: |
| | -INSTALLATION SCHEDULE AND KEY PLAN |
| | DON'T MATCH ARCHITECT'S PLANS. SEE |
| | SIZES OF OPENINGS. ALSO, INSTALLATION |
| | SCHEDULE AND KEY PLAN TO INCLUDE ALL |
| | OPTIONS SHOWN BY THE ARCHITECT. |
| | -CLEARLY INDICATE ON DRAWINGS MOUNTING |
| | CONDITIONS AND ANCHOR TYPE AND SPACING |
| | NOTE: TAKE INTO CONSIDERATION TABLES |
| | ON SHEET 4 OF 4 OF DRAWING 97-404P AND |
| | BUILDING CONSTRUCTION. THE MEAN ROOF |
| | HEIGHT FOR THIS BUILDING IS PLUS OR |
| | MINUS AT 16'-0" AND THE BUILDING CONST |
| | IS REINFORCED MASONRY, NOT CONCRETE. |
| | 6-REVISE ENERGY CALCULATIONS: |
| | -OWNER INFORMATION IS INCORRECT. |
| | -LOCATION IS INCORRECT. |
| | -DON'T FORGET OWNER SIGNATURE AND DATE. |
| | 7-PROVIDE COMPLETE CALCULATIONS FOR |
| | ATTIC CROSS VENTILATION AT EACH UNIT |
| | AND CLEARLY INDICATE ON ROOF PLAN THE |
| | VENT SIZES AND LOCATION. SEC. 2309.7 |
| | 8-PROVIDE COMPLETE DETAIL/SPECIFICATIONS |
| | FOR CEILING CONSTRUCTION AT ENTRY AND |
| | BACK PORCHES OF EACH UNIT. INCLUDE |
| | FASTENER TYPE AND SPACING. SEC. 2504. |
| | 9-WALK-IN-CLOSET IN UNITS 1527 TO HAVE |
| | THE SHELF ONLY (NO ROD) ON EITHER SIDE |
| | IN ORDER TO COMPLY WITH THE CLEARANCES |
| | ON THE FAIR HOUSING ACT, CHAPTER THREE |