| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-REVISE LOCATION OF KITCHEN RANGE TO |
| | COMPLY WITH THE CLEAR SPACE REQUIRED |
| | IN FRONT OF IT. SEC 7A FAIR HOUS'G ACT |
| | 2-BATHROOM #2, UNIT MDL 1409,SEC 7B FHA. |
| | A)DOOR FROM BEDROOM #2 TO BE 32" OPEN'G |
| | B)LENGTH OF BATHROOM DOESN'T HAVE THE |
| | DIMENSION REQUIRED FOR A TYPE A BATH |
| | WHEN APPROACHED FROM THE BEDROOM. |
| | 3-SHOWER AT MASTER BATH TO COMPLY WITH |
| | THE CLEAR FLOOR SPACE REQUIRED. 7B FHA |
| | 4-OPTIONAL SLIDING GLASS DOORS AT MASTER |
| | BEDROOM TO HAVE 32" MIN. CLEAR OPENING |
| | 5-ENTRY DOOR SPACE TO COMPLY W/ANSI 4.13 |
| | 6-ROOF FRAMING PLAN AND TRUSS DRAWINGS: |
| | -CLARIFY CONSTRUCTION AT RIGHT AND LEFT |
| | END OF BUILDING. TRUSS DRAWINGS SHOW |
| | BEARING WALLS AND ARCHITECTURAL DWGS |
| | DON'T. SEE PLANS FOR COMMENTS. |
| | -CLARIFY WHO REVIEW THE TRUSS DRAWINGS. |
| | STAMP SAYS "OUR OFFICE HAS REVIEW..." |
| | WHAT OFFICE IS THIS?. |
| | -CLARIFY WHY THE TRUSSES RUNNING FROM |
| | FRONT TO BACK ARE DESIGNED WITHOUT THE |
| | RIDGE. WHY IS THIS AREA TO BE DONE BY |
| | THE BUILDER?. SPECIFY ALL CONNECTORS. |
| | -UPDATE ALL GENERAL TRUSS DETAILS TO |
| | ASCE 7-95 AND SIGN, SEAL AND DATE THEM |
| | -ENGINEERED TRUSSES TO BE DESIGNED PER |
| | ASCE 7-95 FOR 145 MPH WIND, NOT AS PER |
| | ASCE 7-93 FOR 140 MPH WIND. ALSO, ALL |
| | TRUSSES TO BE DESIGNED USING THE SAME |
| | MEAN ROOF HEIGHT FOR ENTIRE BUILDING. |
| | -REVISE TRUSS ANCHOR SCHEDULE TO RESIST |
| | THE UPLIFT AND LATERAL LOADS SHOWN ON |
| | THE ENGINEERED TRUSSES. |
| | 7-PRODUCT APPROVALS: |
| | -PROVIDE PRODUCT APPROVAL FOR 2 HOUR |
| | CONCRETE BLOCK. |
| | -SLIDING GLASS DOORS AND WINDOW PRODUCT |
| | APPROVALS TO BE SIGNED, SEALED & DATED |
| | BY THE PROFESSIONAL DESIGNER OF RECORD |
| | AND FILL IN THE SPECIFIC JOB LOCATION. |
| | 8-STORM PANELS: |
| | -PROVIDE A COMPLETE INSTALLATION SCHED. |
| | (AS PER CITY SAMPLE) AND THE KEY PLAN. |
| | ALSO, HIGHLIGHT THE SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHOR SPACING. |
| | 9-ENERGY CALCULATIONS TO BE SIGNED AND |
| | DATED BY THE OWNER/AGENT. ALSO, REVISE |
| | THE OWNER INFORMATION ON TOP OF FORM. |
| | -NUMBER OF BEDROOMS ON UNIT 1527 IS 3, |
| | NOT 2. REVISE AS REQUIRED. |
| | 10-PROVIDE CALCULATIONS FOR ATTIC CROSS |
| | VENTILATION AT EACH UNIT.SBC/97 2309.7 |
| | NOTE: TAKE INTO ACCOUNT FIREPROOF DET. |
| | ON WALL SECTION 1 OF SHEET NAMED DT. |
| | 11-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| | CEILING CONSTRUCTION AT ENTRY AND BACK |
| | PORCHES OF EACH UNIT. INCLUDE FASTENER |
| | TYPE AND SPACING. SEC 2504.2 SBC 1997. |
| | 12-DRAWING #4: CLARIFY HOW DOES THE 2 HR |
| | "PARTY WALL" GOES TO THE BOTTOM OF |
| | ROOF SHEATHING IF THE BEAM HEIGHT IS |
| | 12'-11". SEE SECTIONS AND ELEVATIONS. |
| | 13-DETAIL SC-2: HOW DOES THIS DESIGN |
| | MAINTAINS THE STRUCTURAL STABILITY AND |
| | FIRE RESISTANCE IF THE MAIN GIRDER |
| | FAILS. SEC. 704.4.2(3) SBC 1997. |
| | 14-NEED TO HAVE A PERMIT APPLICATION FOR |
| | EACH TOWNHOUSE. |
| | 15-PAY $750 TO THE CITY OF WEST PALM BCH |
| | FOR WESTERN EXPANSION FEES FOR EACH |
| | TOWNHOUSE. |
| | 16-CONSTRUCTION VALUE DECLARED IN THE |
| | PERMIT APPLICATION IS TOO LOW. THE |
| | RECALCULATED VALUE FOR EACH TOWNHOUSE |
| | IS AS FOLLOWS: |
| | $104,640 FOR MODEL 1357 |
| | $107,877 FOR MODEL 1409 AND |
| | $115,660 FOR MODEL 1527 |
| | THEREFORE, PERMIT FEES TO BE ADJUSTED |
| | FOR EACH PERMIT APPLICATION. |
| | 17-PROVIDE SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS FOR COMMENTS.SEC 2405.2 SBC. |
| | 18-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | PLEASE RETURN REVIEWED SET AFTER ALL |
| | CORRECTIONS ARE DONE IN ORDER TO |
| | FACILITATE AND EXPEDITE THE RE-REVIEW |
| | PROCESS. |
| | |
| | |
| | NOTE: |
| | |
| | LEGIBLY PROVIDE THE NAME, ADDRES AND |
| | REGISTRATION NUMBER OF THE ENGINEER |
| | WHO IS SEALING THE ARCHITECTURAL PLANS. |
| | THIS APPLIES TO ALL SETS OF PLANS THAT |
| | ARE SUBMITTED FOR CONSTRUCTION PERMIT. |