| Plan Review Notes For Permit 99121761 |
| Permit Number |
99121761 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | 1.A/C PLAN TO BE SAME AS BUILDING | | | FLOOR PLAN. | | | 2.CFM CALCULATIONS SHOULD BE LESS THAN | | | A/H'S CAPACITY OR LARGER EQUIPMENT | | | SHOULD BE USED. | | | 3.MISSING CFM'S IN UNIT 1527 1-R NOOK. | | | 4.SHOW R/A LOCATION. |
|