| Plan Review Notes For Permit 99121739 |
| Permit Number |
99121739 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-PAY IMPACT FEES. | | | 2-UPDATE/REVISE ALL DRAWINGS. SEE | | | COMMENTS ON PLANS. | | | 3-FOOTING F2 TO BE 16" DEEP MIN. | | | SEC 1804.1.3 SBC 1997. | | | 4-REVISE ELEVATIONS TO MATCH FLOOR PLAN. | | | 5-REVISE SURVEY. THIS PROPERTY IS ON | | | FLOOD ZONE "A8' NOT FLOOD ZONE B. | | | 6-PROVIDE COMPLETE BUCK DETAILS FOR | | | EXTERIOR DOORS, WINDOWS AND GARAGE | | | DOOR. | | | 7-REVISE ENERGY CALCULATIONS. SOUTH IS | | | THE REGION NOT THE CLIMATE ZONE. THE | | | CLIMATE ZONE IS #8. | | | 8-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOOR WITH SIDELITES ASSEMBLY. | | | 9-GARAGE DOOR PRODUCT APPROVAL: | | | -THERE IS NO A LISTING FOR THIS DOORS | | | WITH SBCCI. | | | -DESIGN PRESSURES DON'T MEET THE DESIGN | | | PRESSURES CALCULATED BY THE ENGINEER | | | -DRAWINGS DON'T MATCH REPORT. | | | 10-PROVIDE COMPLETE INFORMATION FOR | | | STORM PANELS (OR INFORMATION MAY BE | | | SUBMITTED LATER UNDER A SEPARATE | | | PERMIT. |
|