2001-01-08 00:00:00************* UNSAT *******************
  
 THESE ARE NOTES THAT WERE ALREADY GIVEN
 AT OTHER TIMES.
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT MAINS!! AND OR PANELS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS. REQ`D BY ARTS;230-65.110-9
 AND 215-5
  
 2)NOTE;AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. PLEASE CORRECT.
  
 3)NOTE: AS REQ`D BY ART;210-8-A-6 ALL
 OUTLETS SERVING KITCHEN COUNTERSPACE
 ARE TO BE GFI/GFI PROTECTED. ALL NEED TO
 BE LABELED THAT WAY.
  
 4)NOTE:PLEASE CORRECT OPTIONAL KITCHEN
 PLAN.
  
 5)NOTE:PLANS DON`T SHOW MAIN DISC.ON THE
 SIDE OF THE HOUSE. WHICH IS CORRECT?
 PLAN OR RISER DIAGRAM?
  
 6)NOTE: AS REQ`D BY 250-81/215-5
 PLEASE SHOW BLDG.STEEL AS THE OTHER
 METHOD OF GROUNDING ELECTRODE CONDUCTOR.
  
 7)NOTE:AS REQ`D BY 210-52D/215-5 PLEASE
 HAVE LISTED ON PANEL SCHEDULE THE DED-
 -ICATED BATH(S) CIRCUT(S) REQ`D TO BE
 20AMP AND #12 AWG.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 CORRECTED AND SUBMITTED FOR REVIEW AND
 APPROVAL. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372.