| 2001-01-08 00:00:00 | ************* UNSAT ******************* |
| | |
| | THESE ARE NOTES THAT WERE ALREADY GIVEN |
| | AT OTHER TIMES. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATING OF |
| | EQUIPMENT MAINS!! AND OR PANELS. |
| | AIC RATING IS FIGURED FROM FAULT CURRENT |
| | CALCULATIONS. REQ`D BY ARTS;230-65.110-9 |
| | AND 215-5 |
| | |
| | 2)NOTE;AS PER NFPA-72 2-2.1.1.1 SMOKE |
| | DETECTORS ARE REQ`D INSIDE AND OUTSIDE |
| | ALL SLEEPING ROOMS. PLEASE CORRECT. |
| | |
| | 3)NOTE: AS REQ`D BY ART;210-8-A-6 ALL |
| | OUTLETS SERVING KITCHEN COUNTERSPACE |
| | ARE TO BE GFI/GFI PROTECTED. ALL NEED TO |
| | BE LABELED THAT WAY. |
| | |
| | 4)NOTE:PLEASE CORRECT OPTIONAL KITCHEN |
| | PLAN. |
| | |
| | 5)NOTE:PLANS DON`T SHOW MAIN DISC.ON THE |
| | SIDE OF THE HOUSE. WHICH IS CORRECT? |
| | PLAN OR RISER DIAGRAM? |
| | |
| | 6)NOTE: AS REQ`D BY 250-81/215-5 |
| | PLEASE SHOW BLDG.STEEL AS THE OTHER |
| | METHOD OF GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 7)NOTE:AS REQ`D BY 210-52D/215-5 PLEASE |
| | HAVE LISTED ON PANEL SCHEDULE THE DED- |
| | -ICATED BATH(S) CIRCUT(S) REQ`D TO BE |
| | 20AMP AND #12 AWG. |
| | |
| | PLEASE HAVE ALL THE ABOVE INFORMATION |
| | CORRECTED AND SUBMITTED FOR REVIEW AND |
| | APPROVAL. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372. |