| Plan Review Notes For Permit 99121731 |
| Permit Number |
99121731 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. NEEDS TO BE ABLE TO | | | HANDLE AVAILABLE FAULT CURRENT. 110-9/ | | | 230-65 | | | | | | 2)NOTE: NEED TO HAVE SMOKE DETECTORS | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | AS REQ`D BY NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: NEED TO SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECTE | | | -D. AS REQ`D BY 210-8-A-6 | | | | | | 4)NOTE:PLEASE INCLUDE BLDG.STEEL AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM. | | | AS PER 250-81 | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REIVEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 X 8372 |
|