| Plan Review Notes For Permit 99121713 |
| Permit Number |
99121713 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING | | | OF EQUIPMENT MAINS.SHOW ON PLANS. | | | AS REQ`D BY ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | | | | 3)NOTEL SHOW MAIN NEXT TO METER ON PLANS | | | | | | 4)NOTE: AS REQ`D BY 210-8-A-6 ALL OUTLET | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | | | | 5)NOTE: PLEASE LIST THE DEDICATED BATH(S | | | CIRCUT ON PANEL SCHEDULE AS REQ`DBY | | | ART; 210-52D/215-5 | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|