| Plan Review Notes For Permit 99121697 |
| Permit Number |
99121697 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS.ALL SERVICE EQUIPMENT | | | MAINS TO BE RATED TO HANDLE AVAILABLE | | | FAULT CURRENT. CAN BE FIGURED FROM | | | FAULT CURRENTCALCULATIONS. ALL AS PER | | | ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE: AS PER NFPA-72 2-2.1.1.1 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | | | | 3)NOTE: PLEASE SHOW THE DEDICATED BATH(S | | | CIRCUT ON PANEL SCHEDULE. AS REQ`D BY | | | ART;210-52D OF THE NEC. | | | | | | 4)NOTE:SHOW MAIN DISC. ON PLANS AS IT | | | IS SHOWN ON RISER DIAGRAM. | | | 5)NOTE: ALL OUTLETS SERVING KITCHEN | | | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED | | | AS PER 210-8-A-6 | | | | | | ALL THE ABOVE INFORMATION NEED TO BE | | | SUBMITTED FOR REVIEW AND APPROVAL. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|