| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT AND NEEDS TO BE ABLE TO HANDLE | | | THE AVAILABLE FAULT CURRENT. | | | | | | 2)NOTE: SMOKE DETECTORS INSIDE AND OUT- | | | -SIDE ALL SLEEPING ROOMS. | | | | | | 3)NOTE: NEED TO HAVE CIRCUT FOR BATH(S) | | | LISTED ON PANEL SCHEDULE AS PER 210-52D | | | 20 AMP AND #12 AWG. | | | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEAS CALL 659-8096 EXT- | | | 8372 |
|