| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE A8. PROVIDE ELEVATION |
| | CERTIFICATE. |
| | 2-REVISE SHEET A-1 AND A-2: DRYER IS NOT |
| | ALLOW TO VENT THRU THE WALL AT ZERO |
| | LOT LINE WALL. TABLE 600 SBC 1997. |
| | 3-SEE COMMENTS ON PLANS AND REVISE/ |
| | UPDATE DRAWINGS AS REQUIRED. |
| | 4-REAR ELEVATION BY FAMILY AREA TO HAVE |
| | THE 34 SH WINDOW OPTION IN ORDER TO |
| | MEET THE TABLE 600 REQUIREMENTS. |
| | 5-SEE PROVISOS BY OTHER TRADES. |
| | 6-RE-SUBMIT GARAGE DOOR PRODUCT APPROVAL |
| | DRAWINGS DON'T MATCH PRODUCT APPROVAL. |
| | WHY FINAL PRODUCT APPROVAL BY SBCCI |
| | DOEN'T HAVE A NUMBER ASSIGNED?. |
| | 7-STORM PANELS: |
| | -INSTALLATION SCHEDULE AND KEY PLAN |
| | DON'T MATCH PLANS. REVISE AS REQUIRED |
| | AND COMPLETE ALL THE INFORMATION AS |
| | REQUESTED ON CITY SAMPLE INSTALLATION |
| | SCHEDULE ATTACHED. |
| | -SEE NOTE #4 ON SHEET 3 OF 5 OF STORM |
| | PANELS DRAWINGS. INSTALLATION SCHED. |
| | CALLS FOR 33" STORM PANELS AND THIS |
| | NOTE CALLS FOR A 40" MIN. STORM PANEL. |
| | REVISE AS REQUIRED. |
| | 8-ENTRY DOOR: |
| | -CLEARLY SPECIFY FASTENERS TO BE USED |
| | ACCORDING TO THE PRODUCT APPROVAL AND |
| | FRAME DETAIL SPECIFIED BY ENGINEER ON |
| | SHEET A-6. |
| | -DRAWINGS IN PRODUCT APPROVAL ARE NOT |
| | CLEAR AND OR IMCOMPLETE. |